SiBE01-503
Check
Service Diagnosis
69
5.3
Outdoor Unit Fan System Check
Check No.09
5.4
Hall IC Check
Check No.16
1. Check the connector connection.
2. With the power ON, operation OFF, and the connector connected, check the following.
∗
Output voltage of about 5 V between pins 1 and 3.
∗
Generation of 3 pulses between pins 2 and 3 when the fan motor is operating.
Failure of (1)
Æ
faulty PCB
Æ
Replace the PCB.
Failure of (2)
Æ
faulty Hall IC
Æ
Replace the fan motor.
Both (1) and (2) result
Æ
Replace the PCB.
Check the
fan motor lead wire
connector for secure
connection.
Abnormal
YES
NO
NO
Continuity
Are the
resistance at connector
leads
∞
? 1. red - black,
2. white - black
Check the fan
capacitor for continuity.
Does the outdoor
fan rotate?
Does
the outdoor unit fan
start just after the power
is turned on?
Check the outdoor fan system.
YES
YES
NO
Normal
No continuity
Repair.
Replace the fan motor.
Replace the fan motor.
Replace the outdoor unit PCB.
The outdoor fan system is
normal.
(R2670)
Summary of Contents for FTYN25DV3B ATY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 13: ...Functions SiBE01 503 4 List of Function...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control...
Page 59: ...Instructions SiBE01 503 50 System Configuration...
Page 79: ...Check SiBE01 503 70 Service Diagnosis...
Page 117: ...Others SiBE01 503 108 Others...