![Daikin FTYN25DV3B ATY20DV2 Service Manual Download Page 26](http://html1.mh-extra.com/html/daikin/ftyn25dv3b-aty20dv2/ftyn25dv3b-aty20dv2_service-manual_4216906026.webp)
SiBE01-503
Functions
Functions and Control
17
1.4
Automatic Operation
Outline
When the automatic mode is selected with the remote controller, the microcomputer determines
the operation mode from cooling and heating according to the room temperature and the
setpoint.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature.
Details of the
Control
Target temperature equals setpoint plus correction value (c1
°
C, heating: –1
°
C)
Mode switching point and operation ON/OFF point are as follows.
Cooling
→
Heating: Room temperature – setpoint
≤
–
2
°
C
Heating
→
Cooling: Room temperature – setpoint
≥
+
2
°
C
Cooling thermostat ON : Room temperature – setpoint
≥
+
2
°
C
Cooling thermostat OFF: Room temperature – setpoint
≤
+
1
°
C
Heating thermostat ON : Room temperature – setpoint
≤
–
2
°
C
Heating thermostat OFF: Room temperature – setpoint
≥
–
1
°
C
Heating
→
Cooling
Cooling thermostat ON
+2˚C
+1˚C
0˚C
–1˚C
–2˚C
Cooling thermostat OFF
Cooling
Heating
Cooling
Compressor ON
Compressor OFF
(R4728)
Heating thermostat OFF
Cooling
→
Heating
Heating thermostat ON
Room temperature – setpoint
Summary of Contents for FTYN25DV3B ATY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 13: ...Functions SiBE01 503 4 List of Function...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control...
Page 59: ...Instructions SiBE01 503 50 System Configuration...
Page 79: ...Check SiBE01 503 70 Service Diagnosis...
Page 117: ...Others SiBE01 503 108 Others...