Outdoor Unit
SiBE01-503
104
Removal Procedure
2
The compressor’s
mounting nut to be
removed is one piece.
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish
fire quickly.
Warning
Ventilate when refrigerant
leaks during the work.(If
refrigerant contacts fire, it will
cause to arise toxic gas).
Caution
Be careful about pipes and so
on, which were heated up by a
gas brazing machine, so as
not to get burnt on your
hands.
Pay attention so that the
heat exchanger’s fins will not
be burnt.
3
Remove the nut by
means of an open-end
wrench.
Begin your work after
recognizing complete
empty of refrigerant in the
refrigerant circuit.
Be sure to apply
nitrogen’s permutation
when heating up the
brazing part.
1
Remove the brazing
part on the compressor
discharge side.
2
Heat up the brazing
part on the compressor
suction part and then
remove it.
3
Lift the compressor and
remove it.
Step
Procedure
Points
Summary of Contents for FTYN25DV3B ATY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 13: ...Functions SiBE01 503 4 List of Function...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control...
Page 59: ...Instructions SiBE01 503 50 System Configuration...
Page 79: ...Check SiBE01 503 70 Service Diagnosis...
Page 117: ...Others SiBE01 503 108 Others...