Check
SiBE01-503
68
Service Diagnosis
5.2
Installation Condition Check
Check No.07
Installation condition check
Normal
Change the position of the air
discharge grille or the
installation location.
Change the position of the air
discharge grille or the
installation location.
Clean the heat exchanger.
Change the installation
location or direction.
Check the outside air
temperature (temperature of air
taken in by the outdoor unit).
(The outside air temperature
shall be 46˚C or lower.)
Check
the allowable
dimensions of the air suction
and discharge
area.
Is
the air flow
blocked by obstacles or
winds blowing in the
opposite direction?
(R4745)
Abnormal
YES
YES
YES
Does
the discharged
air from other outdoor
unit cause an increase of
the suction air
temperature?
NO
NO
NO
Is the heat exchanger
very dirty?
Summary of Contents for FTYN25DV3B ATY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2...
Page 13: ...Functions SiBE01 503 4 List of Function...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control...
Page 59: ...Instructions SiBE01 503 50 System Configuration...
Page 79: ...Check SiBE01 503 70 Service Diagnosis...
Page 117: ...Others SiBE01 503 108 Others...