Control Specification (15/18/24 Class)
SiUS04-904
58
Function and Control
4.12.1 Fully Closing with Power ON
Initialize the electronic expansion valve when turning on the power, set the opening position and
develop pressure equalizing.
4.12.2 Pressure Equalization Control
When the compressor is stopped, open and close the electronic expansion valve and develop
pressure equalization.
4.12.3 Opening Limit
Outline
Limit a maximum and minimum opening of the electronic expansion valve.
Detail
A maximum electronic expansion valve opening : 450 pulses
A minimum electronic expansion valve opening : 54 pulses
The electronic expansion valve is fully closed in the room where cooling is stopped and is opened
with fixed opening during defrosting.
4.12.4 Starting Operation Control
Control the electronic expansion valve opening when the system is starting, and prevent the
system to be superheated or moistened.
4.12.5 High Discharge Pipe Temperature
When the compressor is operating, if the discharge pipe temperature exceeds a certain value, open
the electronic expansion valve and run the refrigerant to the low pressure side and lower discharge
pipe temperature.
4.12.6 Disconnection of the Discharge Pipe Thermistor
Outline
Detect a disconnected discharge pipe thermistor by comparing the discharge pipe temperature with
the condensation temperature. If any is disconnected, open the electronic expansion valve
according to the outdoor air temperature and the operating frequency, and operate for a specified
time, and then stop.
After 3 minutes of waiting, restart the unit and check if any is disconnected. If any is disconnected
stop the system after operating for a specified time. If the disconnection is detected 4 times in
succession, the system shuts down.
Detail
Detect Disconnection
If a 630-second timer for open control becomes over, and a 9-minute timer for the compressor
operation continuation is not counting time, the following adjustment must be made:
1. When the operation mode is cooling
When the discharge pipe temperature is lower than the outdoor heat exchanger temperature,
the discharge pipe thermistor disconnection must be ascertained.
2. When the operation mode is heating
When the discharge pipe temperature is lower than the max temperature of operating room heat
exchanger, the discharge pipe thermistor disconnection must be ascertained.
Adjustment when the thermistor is disconnected
When compressor stop repeats specified time, the system should be down.
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...