Control Specification (15/18/24 Class)
SiUS04-904
52
Function and Control
4.3
Controls at Mode Changing / Start-up
4.3.1 Preheating Operation
Outline
Operate the inverter in the open phase operation with the conditions including the preheating
command from the indoor, the outdoor air temperature and discharge pipe temperature.
Detail
Preheating ON Condition
When outdoor air temperature and discharge pipe temperature are below 51ºF, inverter in open
phase operation starts.
OFF Condition
When outdoor air temperature or discharge pipe temperature is higher than 54ºF, inverter in
open phase operation stops.
4.3.2 Four-Way Valve Switching
Outline
During the heating operation the valve must be energized, and during cooling and defrosting,
current must not be energized. In order to eliminate the switching sound (as the four-way valve coil
switches from ON to OFF) when the heating operation is stopped, the delay switch of the four-way
valve must be carried out after the operation has stopped.
Detail
The OFF delay of four-way valve
Energize the coil for 150 seconds after unit operation is stopped.
4.3.3 Four-Way Valve Operation Compensation
Outline
At the beginning of the operation as the four-way valve is switched, acquire the differential pressure
required for activating the four-way valve by having output frequency, which is more than a certain
fixed frequency, for a certain fixed time.
Detail
Starting Conditions
1. When starting compressor for heating.
2. When the operating mode changes from the previous time.
3. When starting compressor for starting defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
Set the lower limit frequency to 55 (model by model) Hz for 70 seconds with any conditions 1
through 4 above.
4.3.4 3-Minute Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(except when defrosting)
4.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as follows.
(The function must not be used when defrosting.)
FCG 1
FCG 2
FCG 3
TCG1
TCG2
TCG3
55
70
85
120
200
470
(Hz)
(R10540)
Time (Sec)
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...