Main Functions
SiUS04-904
24
Function and Control
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor air
temperature and cooling / heating load.
Quick heating and quick cooling.
The compressor rotational speed is increased when starting the heating (or cooling) operation.
This enables the setpoint to be reached quicker.
Even during extreme cold weather, a high capacity is achieved. It is maintained even when the
outdoor air temperature is 36°F(2°C).
Comfortable air conditioning
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation maintains the temperature at
low power.
Frequency Limits
The following table shows the functions that define the minimum and maximum frequency:
Forced Cooling
Operation
For more information, refer to “Forced operation mode” on page
48
.
1.2
Power-Airflow Dual Louvers, Wide-Angle Fins and Auto-
Swing
Power-Airflow
Dual Louvers
The large louvers send a large volume of air downwards to the floor. The louvers provides an
optimum control area in cooling, heating, and dry mode.
Heating Mode
During heating mode, the large louver directs warm air straight downward and across the floor to
pervade the entire room.
Cooling / Dry Mode
60
120
300
113˚F
Air discharge
temperature
inverter
normal heat pump
Start
seconds
(R4144)
Frequency limits
Limited during the activation of following functions
Low
Four-way valve operation compensation. Refer to page 39.
High
Discharge pipe temperature control. Refer to page 46.
Input current control. Refer to page 40.
Compressor protection function. Refer to page 40.
Heating peak-cut control. Refer to page 42.
Freeze-up protection control. Refer to page 41.
Defrost control. Refer to page 43.
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...