Main Functions
SiUS04-904
26
Function and Control
= Within this range the airflow rate is automatically controlled when the FAN setting button
is set to automatic.
Note:
1. During POWERFUL operation, fan operate H tap + 50 - 90 rpm.
2. Fan stops during defrost operation.
Automatic
Airflow Control
for Heating
In heating mode, the indoor fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room temperature and the required set point.
Automatic
Airflow Control
for Cooling
The following drawing explains the principle of fan speed control for cooling:
1.4
Program Dry Function
Program dry function removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference between
the room temperature at startup and the temperature set by the microcomputer is divided into two
zones. Then, the unit operates in the dry mode with an appropriate capacity for each zone to
maintain the temperature and humidity at a comfortable level.
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R4085)
(R4085)
+
Δ
2.7˚F
+
Δ
0.9˚F
+
Δ
3.6˚F
+
Δ
1.8˚F
M
ML
L
fan speed
Difference between room
and set temperature
Phase control
Thermostat
setting
temperature
(R4146)
Room temperature at
startup
Set temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
75ºF or more
Room temperature at
startup
X
–
4.5ºF (2.5ºC)
X
–
0.9ºF (0.5ºC)
or
Y +
0.9ºF (0.5ºC)
(zone B) continues for
74ºF (23.3ºC)
X
–
3.6ºF (2.0ºC)
X
–
0.9ºF (0.5ºC)
or
Y +
0.9ºF(0.5ºC)
(zone B) continues for
~
64ºF (17.8ºC)
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...