Control Specification (09/12 Class)
SiUS04-904
38
Function and Control
Indoor Frequency Command (
D signal)
The difference between the room temperature and the temperature set by the remote controller is
taken as the “
D signal” and is used for frequency command.
Th OFF = Thermostat OFF
Frequency Initial Setting
<Outline>
When starting the compressor, or when conditions are varied due to the change of the room, the
frequency must be initialized according to the
D value of the indoor unit and the Q value of the
indoor unit.
Q value: Indoor unit output determined from indoor unit volume, airflow rate and other factors.
PI Control (Determine Frequency Up / Down by
D Signal)
1. P control
Calculate
D value in each sampling time (20 seconds), and adjust the frequency according to
its difference from the frequency previously calculated.
2. I control
If the operating frequency is not changed more than a certain fixed time, adjust the frequency up
and down according to the
D value.
When the
D value is small...lower the frequency.
When the
D value is large...increase the frequency.
3. Frequency management when other controls are functioning
When frequency is dropping;
Frequency management is carried out only when the frequency drops.
For limiting lower limit
Frequency management is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set depending on indoor unit.
When low noise commands come from the indoor unit or when outdoor unit low noise or quiet
commands come from indoor unit, the upper limit frequency must be lowered than the usual
setting.
3.3
Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline
Operate the inverter in the open phase operation with conditions including the preheating
command from the discharge pipe temperature.
Detail
Preheating ON Condition
When the discharge pipe temperature is below 50ºF, inverter in open phase operation starts.
(The power consumption of compressor during preheating operation is 35 W.)
OFF Condition
Temperature
difference
°F(°C)
D
signal
Temperature
difference
°F(°C)
D
signal
Temperature
differenc
°F(°C)
D
signal
Temperature
difference
°F(°C)
D
signal
0
Th
OFF
3.6 (2.0)
4
7.2 (4.0)
8
10.8 (6.0)
C
0.9 (0.5)
1
4.5 (2.5)
5
8.1 (4.5)
9
11.7 (6.5)
D
1.8 (1.0)
2
5.4 (3.0)
6
9.0 (5.0)
A
12.6 (7.0)
E
2.7 (1.5)
3
6.3 (3.5)
7
9.8 (5.5
B
13.5 (7.5)
F
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...