SiUS04-904
Main Functions
Function and Control
33
Ex.) : POWERFUL operation in cooling mode.
1.11 Other Functions
1.11.1 Hot-start Function
In order to prevent the cold air blast that normally comes when heating is started, the temperature
of the heat exchanger in the indoor unit is detected, and either the airflow stops or lowers to ensure
comfortable heating of the room.
*The cold air blast is also prevented using a similar control when the defrosting operation is started
or when the thermostat gets turned ON.
1.11.2 Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal receiving
sound.
1.11.3 ON/OFF Button on Indoor Unit
An ON/OFF switch is provided on the front panel of the unit. Use this switch when the remote
controller is missing or if its battery is dead.
Every press of the switch changes from ON to OFF or from OFF to ON
Push this button once to start operation. Push once again to stop it.
This button is useful when the remote controller is missing.
The operation mode refers to the following table.
<Forced operation mode>
Forced operation mode is set by pressing the ON/OFF button for 5 to 9 seconds while the unit is
not operating.
See page 48 for the detail of
Forced Operation Mode
.
Note:
When the ON/OFF button is pressed for 10 seconds or more, the operation is stopped.
(R5488)
Target temp.
Fan
90rpm
Set temp.
64˚F
POWERFUL ON
POWERFUL OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. POWERFUL operation is OFF.
20 min.
ON / OFF button
(R2824)
Mode
Temperature setting
Airflow rate
Heat Pump
AUTO
77ºF
AUTO
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...