Troubleshooting
SiENBE04-401A
114
Service Diagnosis
4.5
Thermistor or Related Abnormality (Indoor Unit)
Remote control
Display
C4, C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation
∗
.
∗
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note:
The values vary slightly in some models.
Supposed
Causes
Faulty connector connection
Faulty thermistor
Faulty PCB
Troubleshooting
Check No.6
Refer to P.140
C4
: Heat exchanger thermistor
C9
: Room temperature thermistor
Check the connector connection.
YE
S
Correct the connection.
Repl
a
ce the thermi
s
tor.
(Repl
a
ce the indoor
u
nit PCB.)
Repl
a
ce the indoor
u
nit PCB.
I
s
it norm
a
l?
I
s
it norm
a
l?
(R140
3
)
NO
Check No. 6
Thermi
s
tor re
s
i
s
t
a
nce check
YE
S
NO
Caution
Be
su
re to t
u
rn off power
s
witch
b
efore connect or di
s
connect connector,
or p
a
rt
s
d
a
m
a
ge m
a
y
b
e occ
u
rred.
Summary of Contents for FTKS20CVMB
Page 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Page 45: ...Specifications SiENBE04 401A 36 Specifications...
Page 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Page 111: ...Instruction SiENBE04 401A 102 System Configuration...
Page 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Page 229: ...Others SiENBE04 401A 220 Others...