SiENBE04-401A
Main Functions
Function and Control
47
1.3
Fan Speed Control for Indoor Units
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and Hall IC control.
For more information about Hall IC, refer to trouble shooting for fan motor on page 113.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Note:
1. During powerful operation, fan operate H tap + 50 - 90 rpm.
2. Fan stops during defrost operation.
Automatic Air
Flow Control for
Heating
The following drawing explains the principle for fan speed control for heating:
Automatic Air
Flow Control for
Cooling
The following drawing explains the principle of fan speed control for cooling:
Step
Cooling
Heating
Dry mode
LLL (Heating thermostat OFF)
25 · 35kW class :
500 - 860 rpm
(During powerful operation :
850 - 910 rpm)
LL (Cooling thermostat OFF)
SL (Silent)
L
ML
M
MH
H
HH (Powerful)
(R4085)
(R4085)
-1.5°C
-1.5°C
-0.5°C
-0.5°C
-1°C
-1°C
-2°C
-2°C
L
ML
M
Phase control
(R2819)
Thermostat
setting
temperature
Difference between room
and set temperature
fan speed
+1.5°C
+1.5°C
+0.5°C
+0.5°C
+2°C
+2°C
+1°C
+1°C
M
ML
L
Thermostat
setting
temperature
(R2820)
fan speed
Difference between room
and set temperature
Phase control
Summary of Contents for FTKS20CVMB
Page 19: ...List of Functions SiENBE04 401A 10 List of Functions...
Page 45: ...Specifications SiENBE04 401A 36 Specifications...
Page 81: ...Control Specification SiENBE04 401A 72 Function and Control...
Page 111: ...Instruction SiENBE04 401A 102 System Configuration...
Page 155: ...Check SiENBE04 401A 146 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 401A 216 Removal Procedure...
Page 229: ...Others SiENBE04 401A 220 Others...