![Daikin FTK25JV1NB9 Service Manual Download Page 33](http://html1.mh-extra.com/html/daikin/ftk25jv1nb9/ftk25jv1nb9_service-manual_2459333033.webp)
General Functionality
Si04-115
24
Main Function
1.5
Forced Operation Mode
Forced mode
A way to enter the test operation mode by a remote controller.
1. Set on the desirous mode and push ON/OFF button. (operation ON)
2. Two buttons; Center of temperature set buttons “
”, and “ Mode” button, should be
pushed simultaneously. (then a left figure of the liquid crystal temperature’s display number
starts to blink.)
3. Moreover, push “MODE” button twice. (If the liquid crystal display becomes “
”, the test
operation mode will startup under the mode displayed in a liquid crystal.)
Item
Forced cooling
Forced heating
Conditions
"
not in the 3-minute stand-by mode
"
normal operation mode
"
outdoor unit off
"
no malfunction in the outdoor unit
"
forced mode: cooling mode.
"
not in the 3-minute stand-by mode
"
normal operation mode
"
outdoor unit off
"
no malfunction in the outdoor unit
"
forced mode: heating mode.
Start
Adjustment
1. Keep pushing the operation switch of
the indoor unit for 5 to 10 seconds.
2. Change the remote controller setting to
a cooling test operation.
(Regarding a way to enter the test
operation, refer to the note in a margin
below)
Possible to enter the forced cooling mode
by either way of 1. or 2..
"
Fix operation frequency to 66 Hz.
"
Operation-on timer :15 min.
"
Indoor unit’s fan : H tap.
"
Swing flap: the latest set position.
With a change of the remote controller
setting to a heating test operation, the unit
enters the forced heating mode.
(Regarding a way to enter the test
operation mode, refer to the note in a
margin below)
"
Fix operation frequency to 66 Hz.
"
Operation-on timer :15 min.
"
Indoor unit’s fan : H tap.
"
Swing flap: the latest set position.
Reset
1. Push the operation switch of the indoor
unit in an usual way.
2. Push the stop button on a remote
controller.
3. Operation-on timer : 15 min. overtime.
1. Push the operation switch of the indoor
unit in an usual way.
2. Push the stop button on a remote
controller.
3. Operation-on timer : 15 min. overtime.
TEMP