Specifications
SiBE04-101
6
Specifications
1.2
Floor / Ceiling Suspended Dual Type
230V 50Hz
Notes:
MAX. interunit piping length: 30m
MAX. interunit height difference: 20m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
The Fan Control of the Outdoor Unit on the Outdoor Conditions Less than 10˚C (In Cool Operation)
Models
Indoor Units
FLX50JV1B
FLX60JV1B
Outdoor Units
RXD50JV1B
RXD60JV1B
Cooling
Heating
Cooling
Heating
Capacity
Rated (Min.~Max.)
kW
4.7 (0.9~5.3)
6.1 (0.9~7.5)
5.7 (0.9~6.5)
6.7 (0.9~8.0)
Btu/h
16,000 (3,100~18,100)
20,800 (3,100~25,600)
19,500 (3,100~22,200)
22,900 (3,100~27,300)
kcal/h
4,040 (775~4,560)
5,250 (775~6,450)
4,900 (775~5,590)
5,760 (775~6,880)
Moisture Removal
L/h
2.9
—
3.9
—
Running Current (Rated)
A
6.4
8.0
8.7
8.7
Power Consumption Rated
(Min.~Max.)
W
1,470 (450~1,950)
1,820 (450~2,630)
1,990 (450~2,670)
2,000 (450~3,300)
Power Factor
%
99.9
98.9
99.5
100.0
COP
W/W
3.20
3.35
2.86
3.35
Piping
Connections
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
15.9
Drain
mm
φ
18.0
φ
18.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Indoor Units
FLX50JV1B
FLX60JV1B
Front Panel Color
Almond White
Almond White
Air Flow Rate
m
³
/min
(cfm)
H
11.4 (402)
12.1 (427)
12.0 (424)
12.8 (452)
M
9.9 (349)
9.8 (346)
10.6 (374)
10.6 (374)
L
8.5 (300)
7.5 (265)
9.3 (328)
8.4 (297)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
34
34
Speed
Steps
5 Steps and Auto
5 Steps and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removable / Washable / Mildew Proof
Removable / Washable / Mildew Proof
Running Current (Rated)
A
0.43
0.42
0.45
0.43
Power Consumption (Rated)
W
96
96
98
96
Power Factor
%
97.1
99.4
94.7
97.1
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H
×
W
×
D)
mm
490
×
1,050
×
200
490
×
1,050
×
200
Packaged Dimensions (W
×
D
×
H)
mm
1,100
×
566
×
284
1,100
×
566
×
284
Weight
kg
17
17
Gross Weight
kg
24
24
Operation
Sound
H/M/L
dBA
47/43/39
46/41/35
48/45/41
47/42/37
Outdoor Units
RXD50JV1B
RXD60JV1B
Casing Color
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
2YC32YXD2YC45ZXD
Motor Output
W
1,500
1,900
Refrigerant
Oil
Model
SUNISO 4GSD.I.
SUNISO 4GSD.I.
Charge
L
0.4
0.75
Refrigerant
Model
R22
R22
Charge
kg
1.15
1.60
Air Flow Rate
(H/L)
m
³
/min (cfm)
H
48.0 (1,694)
42.6 (1,504)
46.5 (1,641)
45.6 (1,610)
L
36.0 (1,271)
31.4 (1,108)
36.5 (1,288)
35.0 (1,236)
Fan
Type
Propeller
Propeller
Motor Output
W
53
53
Running Current (Rated)
A
5.97
7.58
8.25
8.27
Power Consumption (Rated)
W
1,374
1,724
1,892
1,904
Power Factor
%
100.0
98.9
99.7
100.0
Starting Current
A
8.0
8.7
Dimensions (H
×
W
×
D)
mm
735
×
825
×
300
735
×
825
×
300
Packaged Dimensions (W
×
D
×
H)
mm
929
×
359
×
784
929
×
359
×
784
Weight
kg
44
51
Gross Weight
kg
48
55
Operation Sound
dBA
47
48
48
49
Drawing No.
3D029186
3D029187
Conversion Formulae
kcal/h=kW
×
860
Btu/h=kW
×
3414
cfm=m
³
/min
×
35.3
Cooling
Heating
Piping Length
Indoor ; 27˚CDB/19˚CWB
Outdoor ; 35˚CDB/24˚CWB
Indoor ; 20˚CDB
Outdoor ; 7˚CDB/6˚CWB
7.5m
RXD50JV1B
RXD60JV1B
Fan Motor Rotation Speed (rpm)
LL
280
320
LLL
200
200
Air Flow Rate (m
³
/min)
LL
17.0
19.0
LLL
11.0
11.0
The Outdoor Temperature (˚C)
LL
0˚C~10˚C
0˚C~10˚C
LLL
Less than 0˚C
Less than 0˚C
SiBE04-101.book Page 6 Monday, October 15, 2001 3:08 PM