For RXD50·60·71J
SiBE04-101
144
Removal Procedure
1.6
Removal of Motorized Valve
Procedure
Warning Be sure to turn off all power supplies before disassembling work.
Step
Procedure
Points
1
Remove the motorized
valve coil.
2
Remove the 4-way valve
coil.
3
Remove the putty.
4
Get rid of the brazing at
the points (a) and (b) in
this order.
Warning
If refrigerant gas leaks during the
job, ventilate the room. (Bear in
mind that if the refrigerant gas is
exposed to open flames, noxious
gas may be generated.)
Caution
Be careful not to get yourself burnt
with the pipes and other parts that
are heated by the gas welding rod.
Be careful not to burn the heat
exchanger fins.
Reassembling precautions
Wrap the 4-way valve with wet
cloth. Splash water over the
cloth against becoming too hot.
SiBE04-101.book Page 144 Monday, October 15, 2001 3:08 PM