General Functions
SiBE04-101
44
Main Function
1.23
On-site Setting Jumper Wire
Outline
It is necessary to provide the specifications which may be required for the measures to be taken according
to the local circumstances of the installation site. If necessary, such specifications can be adopted easily
by cutting the jumper wire provided on the PCB of outdoor unit.
1. Jumper wire for disposal of remaining frost after defrosting operation
By cutting the jumper wire "J400" on the PCB, the compressor operation frequency in defrosting operation
is increased by 4Hz and the maximum defrosting time is extended by 90 seconds.
2. Jumper wire for decreasing upper limit frequency in outdoor unit silent operation
By cutting the jumper wire "J250" on the PCB, the compressor operation upper limit frequency in outdoor
unit silent operation is decreased by 10Hz and the silencing performance is enhanced.
Refer “Control PCB” on page 14 for J400 Jumper.
Refer “Control PCB” on page 14 for J250 Jumper.