Installation manual

9

FCQG35~1 FCQHG71~140FVEB

Split System air conditioners

3P308369-1C – 2012.10

Setting indoor unit number of simultaneous operation 
system

When using in simultaneous operation system mode, change the
Second code No. as shown in the table. (Second code No. is factory
set to "01" for 1 connected unit.)

When using in simultaneous operation system mode, refer to

"Simultaneous operation system individual setting" on page 9

 to set

master and slave units separately.

When using wireless remote controllers

When using wireless remote controllers, wireless remote controller
address setting is necessary. Refer to the installation manual
attached to the wireless remote controller for setting instructions.

Simultaneous operation system individual setting

It is easier if the optional remote controller is used when setting the
slave unit.

Perform the following procedures when setting the master and slave
unit separately.

Procedure 

(See figure 17)

1

Change the Second code No. to "02", individual setting, so that
the slave unit can be individually set. (Second code No. is
factory set to "01", unified setting.)

2

Perform field setting for the master unit.

3

Turn off the main power supply switch after (2).

4

Detach remote controller from the master unit and connect it to
the slave unit.

5

Turn on the main power supply switch again, and as in (1),
change the Second code No. to "02", individual setting.

6

Perform field setting for the slave unit.

7

Turn off the main power supply switch after (6).
In case there are 2 or more slave units, repeat steps (4) to (7) for
all slave units.

8

Detach the remote controller from the slave unit after the setting,
and reattach to the master unit. This is the end of the setting
procedure.

You do not need to rewire the remote controller from the master unit if
the optional remote controller for slave unit is used. (However,
remove the wires attached to the remote controller terminal board of
the master unit.)

T

EST

 

OPERATION

Refer to 

"For the following items, take special care during

construction and check after installation is finished" on page 2

.

After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.

Test operation after installing decoration panel

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 

 4 times

(2 times for wireless remote controller) and operate at Test
Operation mode for 3 minutes.

6

Push air flow direction adjust button 

 to make sure

the unit is in operation.

7

Press Inspection/Test Operation button 

 and operate

normally.

8

Confirm function of unit according to the operation manual.

Test operation before installing decoration panel 

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set to cooling operation with the wired remote controller and
start operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 

 4 times and

operate at Test Operation mode for 3 minutes.

6

Press Inspection/Test Operation button 

 and operate

normally.

7

Confirm function of unit according to the operation manual.

8

Turn off the main power supply after operation.

Precautions

1

In case something is wrong with the unit and it does not operate,
refer to the installation manual attached to the outdoor unit or
contact your dealer.

2

Refer to the installation manual attached to the outdoor unit in
case of Individual Operation System type.

3

Conduct test operation after installing decoration panel if the
wireless remote controller is used.

Setting

Mode No.

First code 

No.

Second 

code No.

Pair system (1 unit)

11 (21)

0

01

Simultaneous operation 

system (2 unit)

02

Simultaneous operation 

system (3 unit)

03

Simultaneous operation 

system (4 unit)

04

1

Main power supply

2

Main switch

3

Fuse

4

Remote controller (optional accessories)

5

Indoor unit (Master)

6

Indoor unit (Slave)

Setting

Mode No.

First code No.

Second code 

No.

Unified setting

11 (21)

1

01

Individual setting

02

NOTE

Do not touch the drain pump, this may cause electrical
shock.

/TEST

SWING

/TEST

/TEST

/TEST

Summary of Contents for FCQG100FVEB

Page 1: ...INSTALLATION MANUAL FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB FCQHG71FVEB FCQHG100FVEB FCQHG125FVEB FCQHG140FVEB Split System air conditioners...

Page 2: ...2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 1 2 5 4 10 15 mm 10 15 mm 70 90 mm 7 mm 70 90 mm 2 8 4 2 2 5 6 5 6 7 6 1 9 7...

Page 3: ...e acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o C...

Page 4: ...ol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factories Also in vehicles or vessels When selecting the install...

Page 5: ...oller when installing the unit at a height over 2 7 m for FCQHG100 140 units 3 2 m Install the unit higher than 2 5 m to avoid accidental touching Refer to Field setting on page 8 and to the decoratio...

Page 6: ...gure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The c...

Page 7: ...inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening rmly If the refrigerant gas leaks during the work ventilate the area A toxic gas is emitted by t...

Page 8: ...clamp and drain hose to insulate and x it with clamps Insulate the complete drain piping inside the building eld supply If the drain hose cannot be suf ciently set on a slope t the hose with drain rai...

Page 9: ...that the operation will restart automatically if the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power s...

Page 10: ...table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done ll in any gaps in the casing wiring holes with putty or insulation material eld s...

Page 11: ...and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according to the table below so...

Page 12: ...ion and check after installation is nished on page 2 After nishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit Test o...

Page 13: ...or switch wireless address set Adaptor for wiring F1U F2U Fuse 5 A 250 V KCR Magnetic relay KFR Magnetic relay KHuR Magnetic relay Connector for optional parts X2A Connector sensor kit X8A Connector a...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...3P308369 1C 2012 10 Copyright 2011 Daikin...

Reviews: