Installation manual

5

FCQG35~1 FCQHG71~140FVEB

Split System air conditioners

3P308369-1C – 2012.10

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

D

RAIN

 

PIPING

 

WORK

Installation of drain piping

Install the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
-

Keep piping as short as possible and slope it downwards at a 
gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Push the supplied drain hose as far as possible over the 
drain socket.

-

Tighten the metal clamp until the screw head is less than 
4 mm from the metal clamp part as indicated in the 
illustration.

-

After the testing of drain piping is finished, attach the drain 
sealing pad (4) supplied with the unit over the uncovered part 
of the drain socket (= between drain hose and unit body).

-

Wrap the supplied large sealing pad over the metal clamp 
and drain hose to insulate and fix it with clamps.

-

Insulate the complete drain piping inside the building (field 
supply).

-

If the drain hose cannot be sufficiently set on a slope, fit the 
hose with drain raising piping (field supply).

How to perform piping 

(See figure 7)

-

Connect the drain hose to the drain raising pipes, and 
insulate them.

-

Connect the drain hose to the drain outlet on the indoor unit, 
and tighten it with the clamp.

Precautions
-

Install the drain raising pipes at a height of less than 675 mm.

-

Install the drain raising pipes at a right angle to the indoor 
unit and no more than 300 mm from the unit.

-

To prevent air bubbles, install the drain hose level or slightly 
tilted up (

75 mm).

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

2

3

4

5

6

6

1

1-1.5 m

2

1

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Drain sealing pad (supplied with the unit)

5

Large sealing pad (supplied with the unit)

6

Drain piping (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Metal clamp (supplied with the unit)

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 9

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

6

2

4

3

5

4 mm

3
5

2

A

A'

A-A'

1

Summary of Contents for FCQG100FVEB

Page 1: ...INSTALLATION MANUAL FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB FCQHG71FVEB FCQHG100FVEB FCQHG125FVEB FCQHG140FVEB Split System air conditioners...

Page 2: ...2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 1 2 5 4 10 15 mm 10 15 mm 70 90 mm 7 mm 70 90 mm 2 8 4 2 2 5 6 5 6 7 6 1 9 7...

Page 3: ...e acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o C...

Page 4: ...ol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factories Also in vehicles or vessels When selecting the install...

Page 5: ...oller when installing the unit at a height over 2 7 m for FCQHG100 140 units 3 2 m Install the unit higher than 2 5 m to avoid accidental touching Refer to Field setting on page 8 and to the decoratio...

Page 6: ...gure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The c...

Page 7: ...inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening rmly If the refrigerant gas leaks during the work ventilate the area A toxic gas is emitted by t...

Page 8: ...clamp and drain hose to insulate and x it with clamps Insulate the complete drain piping inside the building eld supply If the drain hose cannot be suf ciently set on a slope t the hose with drain rai...

Page 9: ...that the operation will restart automatically if the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power s...

Page 10: ...table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done ll in any gaps in the casing wiring holes with putty or insulation material eld s...

Page 11: ...and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according to the table below so...

Page 12: ...ion and check after installation is nished on page 2 After nishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit Test o...

Page 13: ...or switch wireless address set Adaptor for wiring F1U F2U Fuse 5 A 250 V KCR Magnetic relay KFR Magnetic relay KHuR Magnetic relay Connector for optional parts X2A Connector sensor kit X8A Connector a...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...3P308369 1C 2012 10 Copyright 2011 Daikin...

Reviews: