FCQG35~1 FCQHG71~140FVEB
Split System air conditioners
3P308369-1C – 2012.10

Installation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 3 or
4 (closed corners) directions.

Install the unit so that air vents, lights, or machines near the unit do
not interfere with the air flow.

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where there is no risk of flammable gas leaking.

The equipment is not intended for use in a potentially explosive
atmosphere.

Where piping between indoor and outdoor units is possible within the
allowable limit. (Refer to the installation manual of the outdoor unit.)

Keep indoor unit, outdoor unit, inter unit wiring and remote
controller wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
1 meter is kept.)

When installing the wireless remote controller kit, the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights who are electrically started
in the room. The indoor unit must be installed as far as possible
away from fluorescent lights.

2

Ceiling height

This indoor unit may be installed on ceilings up to 3.5 m in height
(for FCQHG100~140 units: 4.2 

m). However, it becomes

necessary to make field settings using the remote controller
when installing the unit at a height over 2.7 

m (for

FCQHG100~140 units: 3.2 m).
Install the unit higher than 2.5 m to avoid accidental touching.
Refer to 

"Field setting" on page 8

 and to the decoration panel

installation manual.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 3 directions, it is necessary to
make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to 

"Field setting" on page 8

(See

figure 1)

 (

: air flow direction)

4

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

 (

: air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 3)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

a

Indoor unit

b

Lighting
The figure describes about a ceiling lighting, but a recessed 
ceiling light is not restricted.

c

Air fan

A

If the air outlet is closed, space marked (A) should be 500 mm at 
least. In addition, if both the right and left corner of this air outlet 
are closed, space marked (A) should be 200 mm at least.

B

1500 mm from any static volume

1500 mm

2000 mm

4000 mm

(

A

)

1500 mm

(

B

)

1500 mm

a

c

b

a

1

All-round air discharge

2

Air discharge in 4 directions

3

Air discharge in 3 directions

NOTE

Air flow directions as shown in 

figure 1

 merely

serve as examples of possible air flow directions.

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *, on
sides where the air outlet is closed.

Model

H

Model

H

FCQG35~71

214

FCQHG71~140

298

FCQG100~140

256

Summary of Contents for FCQG100FVEB

Page 1: ...INSTALLATION MANUAL FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB FCQHG71FVEB FCQHG100FVEB FCQHG125FVEB FCQHG140FVEB Split System air conditioners...

Page 2: ...2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 1 2 5 4 10 15 mm 10 15 mm 70 90 mm 7 mm 70 90 mm 2 8 4 2 2 5 6 5 6 7 6 1 9 7...

Page 3: ...e acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o C...

Page 4: ...ol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factories Also in vehicles or vessels When selecting the install...

Page 5: ...oller when installing the unit at a height over 2 7 m for FCQHG100 140 units 3 2 m Install the unit higher than 2 5 m to avoid accidental touching Refer to Field setting on page 8 and to the decoratio...

Page 6: ...gure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The c...

Page 7: ...inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening rmly If the refrigerant gas leaks during the work ventilate the area A toxic gas is emitted by t...

Page 8: ...clamp and drain hose to insulate and x it with clamps Insulate the complete drain piping inside the building eld supply If the drain hose cannot be suf ciently set on a slope t the hose with drain rai...

Page 9: ...that the operation will restart automatically if the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power s...

Page 10: ...table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done ll in any gaps in the casing wiring holes with putty or insulation material eld s...

Page 11: ...and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according to the table below so...

Page 12: ...ion and check after installation is nished on page 2 After nishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit Test o...

Page 13: ...or switch wireless address set Adaptor for wiring F1U F2U Fuse 5 A 250 V KCR Magnetic relay KFR Magnetic relay KHuR Magnetic relay Connector for optional parts X2A Connector sensor kit X8A Connector a...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...3P308369 1C 2012 10 Copyright 2011 Daikin...

Reviews: