6

Testing of drain piping

After the piping work is finished, check if drainage flows smoothly.

Add approximately 1 

l of water gradually through the air

discharge outlet.
Method of adding water 

(See figure 11)

Check the drainage flow.

In case electric wiring work is finished
Check drainage flow during COOL running, explained in 

"Test

operation" on page 9

.

In case electric wiring work is not finished

-

Remove the control box lid. Connect the single-phase
power supply (50 Hz, 230 V) to connections No. 1 and
No. 2 on the inter unit wiring terminal block and connect
the ground wire firmly (see 

figure 10

).

-

Reattach the control box lid and turn on the power.

-

Do not touch the drain pump. It may result in electric
shock.

-

Confirm the drain operation looking at the drain socket.

-

After checking the drainage flow, turn off power, remove
the control box lid and disconnect the single phase power
supply from the inter unit wiring terminal block again.
Attach the control box lid as before.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and national
regulations.

Use copper wire only.

Follow the 'Wiring diagram' attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the earth leakage circuit breaker and fuse,
and wiring instructions.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause 
abnormally high electric potential in the ground during 
lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is 
used.

Electrical characteristics

Specifications for field wire

1

Plastic watering can (tube should be about 100 mm long)

2

Service drain outlet (with rubber plug) (Use this outlet to 
drain water from the drain pan)

3

Drain pump location

4

Drain pipe

5

Drain socket (water flow view point)

1

Control box lid

2

Inter unit wiring

3

Earth cable

4

Inter unit wiring terminal block

5

Clamp

6

Transmission wiring

7

Terminal board for transmission wiring

8

Opening for cables

9

Wiring diagram label
(on the back side of the control box lid)

10

Remote controller wiring

Inter unit wiring terminal block (4) 

1

2

NOTE

For details, refer to "Electrical data".

Wire

Size (mm

2

)

Length

Between 

indoor units

H05VV-U4G

(1),(2)

(1) Shows only in case of protected pipes. Use H07RN-F in case of no protection.
(2) Run transmission wiring between the indoor and outdoor units through a conduit 

to protect against external forces, and feed the conduit through the wall together 
with refrigerant piping.

2,5

Unit-Remote 

controller

Sheathed wire 

(2 wire)

(3)

(3) Use double insulation wire for remote controller (sheath thickness: 

1 mm) or run 

wires through a wall or conduit so that the user cannot come in contact with them.

0.75-1.25

500 m

(4)

(4) This length is the total maximum extended length in the system in case of group 

control.

Summary of Contents for FCQG100FVEB

Page 1: ...INSTALLATION MANUAL FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB FCQHG71FVEB FCQHG100FVEB FCQHG125FVEB FCQHG140FVEB Split System air conditioners...

Page 2: ...2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 1 2 5 4 10 15 mm 10 15 mm 70 90 mm 7 mm 70 90 mm 2 8 4 2 2 5 6 5 6 7 6 1 9 7...

Page 3: ...e acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o C...

Page 4: ...ol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factories Also in vehicles or vessels When selecting the install...

Page 5: ...oller when installing the unit at a height over 2 7 m for FCQHG100 140 units 3 2 m Install the unit higher than 2 5 m to avoid accidental touching Refer to Field setting on page 8 and to the decoratio...

Page 6: ...gure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The c...

Page 7: ...inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening rmly If the refrigerant gas leaks during the work ventilate the area A toxic gas is emitted by t...

Page 8: ...clamp and drain hose to insulate and x it with clamps Insulate the complete drain piping inside the building eld supply If the drain hose cannot be suf ciently set on a slope t the hose with drain rai...

Page 9: ...that the operation will restart automatically if the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power s...

Page 10: ...table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done ll in any gaps in the casing wiring holes with putty or insulation material eld s...

Page 11: ...and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according to the table below so...

Page 12: ...ion and check after installation is nished on page 2 After nishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit Test o...

Page 13: ...or switch wireless address set Adaptor for wiring F1U F2U Fuse 5 A 250 V KCR Magnetic relay KFR Magnetic relay KHuR Magnetic relay Connector for optional parts X2A Connector sensor kit X8A Connector a...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...3P308369 1C 2012 10 Copyright 2011 Daikin...

Reviews: