Installation manual

7

FCQG35~1 FCQHG71~140FVEB

Split System air conditioners

3P308369-1C – 2012.10

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 10)

Inter unit wiring
Remove the control box lid (1) and connect the inter unit wiring
terminal block inside with the matching numbers and connect
the ground wire to the grounding terminal. While doing this, pull
the wires inside through the hole in the casing and clamp the
wires along with other wires using a clamp as indicated in the
figure.

Remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the remote controller wiring
terminal block. Securely fix the wiring using a clamp as indicated
in the figure.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.

Attach the control box lid

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

-

Use a round crimp-style terminal for insulation sleeve for 
connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When clamping wiring, use the clamps (delivered with the 
unit) to prevent outside pressure being exerted on the wiring 
connections. Tie up firmly. When doing the wiring, make sure 
the wiring is neat and does not cause the control box to stick 
up. Close the cover firmly.

-

When connecting wires of the same gauge, connect them 
according to the figure.

Use the specified electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. Use torques according to the table
below.

-

When attaching the control box lid, make sure not to pinch 
any wires.

-

After all wiring connections are done, fill in any gaps in the 
casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller wiring should be located at least 50 mm away
from inter unit wiring and other wiring. Not following this
guideline may result in malfunction due to electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the inter unit wiring to the remote controller wiring.
This mistake could damage the entire system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worst case, electric shock
or fire.

1

Control box lid

2

Inter unit wiring

3

Earth cable

4

Inter unit wiring terminal block

5

Clamp (field supply)

6

Remote controller wiring

7

Remote controller wiring terminal block

8

Opening for cables

9

Wiring diagram label (on the back side of the control box lid)

Tightening torque (N•m)

Terminal block for remote controller

0.79~0.97

Terminal block for wiring the units

1.18~1.44

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

NOTE

The customer has the ability to select the remote
controller thermistor.

Summary of Contents for FCQG100FVEB

Page 1: ...INSTALLATION MANUAL FCQG35FVEB FCQG50FVEB FCQG60FVEB FCQG71FVEB FCQG100FVEB FCQG125FVEB FCQG140FVEB FCQHG71FVEB FCQHG100FVEB FCQHG125FVEB FCQHG140FVEB Split System air conditioners...

Page 2: ...2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 1 2 5 4 10 15 mm 10 15 mm 70 90 mm 7 mm 70 90 mm 2 8 4 2 2 5 6 5 6 7 6 1 9 7...

Page 3: ...e acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o C...

Page 4: ...ol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage uctuates a lot e g in factories Also in vehicles or vessels When selecting the install...

Page 5: ...oller when installing the unit at a height over 2 7 m for FCQHG100 140 units 3 2 m Install the unit higher than 2 5 m to avoid accidental touching Refer to Field setting on page 8 and to the decoratio...

Page 6: ...gure 6 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The c...

Page 7: ...inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening rmly If the refrigerant gas leaks during the work ventilate the area A toxic gas is emitted by t...

Page 8: ...clamp and drain hose to insulate and x it with clamps Insulate the complete drain piping inside the building eld supply If the drain hose cannot be suf ciently set on a slope t the hose with drain rai...

Page 9: ...that the operation will restart automatically if the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power s...

Page 10: ...table below When attaching the control box lid make sure not to pinch any wires After all wiring connections are done ll in any gaps in the casing wiring holes with putty or insulation material eld s...

Page 11: ...and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according to the table below so...

Page 12: ...ion and check after installation is nished on page 2 After nishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit Test o...

Page 13: ...or switch wireless address set Adaptor for wiring F1U F2U Fuse 5 A 250 V KCR Magnetic relay KFR Magnetic relay KHuR Magnetic relay Connector for optional parts X2A Connector sensor kit X8A Connector a...

Page 14: ......

Page 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Page 16: ...3P308369 1C 2012 10 Copyright 2011 Daikin...

Reviews: