2 Specific installer safety instructions
Installation and operation manual
4
FAA71+100BUV1B
Split system air conditioner
3P654518-1A – 2021.03
2
Specific installer safety
instructions
Always observe the following safety instructions and regulations.
General
WARNING
Make sure installation, servicing, maintenance, repair and
applied materials follow the instructions from Daikin and, in
addition, comply with applicable legislation and are
performed by qualified persons only. In Europe and areas
where IEC standards apply, EN/IEC 60335-2-40 is the
applicable standard.
Unit installation (see
12])
WARNING
The appliance using R32 refrigerant shall be stored so as
to prevent mechanical damage and in a well-ventilated
room without continuously operating ignition sources (e.g.
open flames, an operating gas appliance, or an operating
electric heater). The room size shall be as specified in the
General safety precaution.
CAUTION
For walls containing a metal frame or a metal board, use a
wall embedded pipe and wall cover in the feed-through
hole to prevent possible heat, electrical shock, or fire.
Refrigerant piping installation (see
CAUTION
Piping MUST be installed according to instructions given in
16]. Only mechanical joints (e.g.
braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this unit to guarantee its
lifetime. The drying material may dissolve and damage
the system.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
CAUTION
Install the refrigerant piping or components in a position
where they are unlikely to be exposed to any substance
which may corrode components containing refrigerant,
unless the components are constructed of materials that
are inherently resistant to corrosion or are suitably
protected against corrosion.
17])
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
For the user
3
User safety instructions
Always observe the following safety instructions and regulations.
3.1
General
WARNING
If you are NOT sure how to operate the
unit, contact your installer.