14 Electrical installation

Installation and operation manual

17

FAA71+100BUV1B
Split system air conditioner
3P654518-1A – 2021.03

13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

13.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: MILDLY FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

Pipe length

. Keep refrigerant piping as short as possible.

1

Flare connections

. Connect refrigerant piping to the unit using

flare connections.

2

Insulation

.  Insulate  the  refrigerant  piping,  the  insulating  tape

should  be  wrapped  from  the  L-shaped  bend  all  the  way  to  the
end inside the unit as follows:

d

f

b

e

g

a

c

h

d

b

i

a

Field piping

b

Indoor unit piping insulation tubing

c

Indoor unit piping

d

Insulating tubing tape

e

Insulating tape (accessory)

f

Large tie wrap (accessory)

g

Beginning of wrapping

h

L-shaped bend

i

Insulation tubing seam (make sure there are no gaps in
the insulation tubing seam)

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

14.1

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

4-core cable

1.5 mm

2

~2.5 mm

2

 and

applicable for 220~240 V

H05RN-F (60245 IEC 57)

(a)

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

H03VV-F (60227 IEC 52)

Maximum 500 m

(a)

In case the conduit pipes are not used, use H07RN-F (60245 IEC
66).

14.2

To connect the electrical wiring to
the indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For  instructions  on  how  to  connect  the  optional

equipment,  see  the  installation  manual  delivered  with
the optional equipment.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover and shield plate.

2

User  interface  cable

:  Connect  the  cable  to  the  terminal  block

(symbols P1, P2).

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Seal  all  gaps  with  a  sealing  material  (field  supply)  to  prevent
small animals from entering the system.

5

Reattach the shield plate and the service cover.

Summary of Contents for FAA-B

Page 1: ...Installation and operation manual Split system air conditioner English Installation and operation manual Split system air conditioner FAA71BUV1B FAA100BUV1B...

Page 2: ...na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus normi...

Page 3: ...to the indoor unit 17 15 Finishing the indoor unit installation 19 15 1 To fix the unit on the mounting plate 19 16 Commissioning 19 16 1 Checklist before commissioning 19 16 2 To perform a test run 2...

Page 4: ...ay cause refrigerant gas leakage CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refri...

Page 5: ...nd human health For more information contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household was...

Page 6: ...ION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch before executing any maintenance task CAUTION Do NOT insert fingers rods o...

Page 7: ...ing unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electric shock or fire Contact your dealer 4 About the system WARNING Do NOT modify disassemb...

Page 8: ...40 Outdoor temperature 15 46 C DB 15 15 5 C WB Indoor temperature 14 28 C WB 10 27 C DB Indoor humidity 80 a a To avoid condensation and water dripping out of the unit If the temperature or the humidi...

Page 9: ...on as desired What The system directs the airflow differently depending on the user selection CAUTION ALWAYS use a user interface to adjust the angle of the flap When the flap is swinging and you move...

Page 10: ...terminals of main circuit capacitors or electrical components before servicing 7 2 Cleaning the unit CAUTION Turn off the unit before cleaning the air outlet exterior front panel and air filter 7 2 1...

Page 11: ...e of the refrigerant total refrigerant charge in kg 1000 Please contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly f...

Page 12: ...of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport Unpack the indoor unit completely according to the instructions mention...

Page 13: ...ting plate 1 Remove the mounting plate from the unit Remove 2 screws from class 71 or 1 screw from class 100 Push the knobs in the direction of the arrow Remove the mounting plate A b a b 1 1 c 2 c 2...

Page 14: ...ary fixing hole 12 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electr...

Page 15: ...trical wiring and the refrigerant pipes together using vinyl tape field supply c e f b d a A A c g a Drain hose b Wall hole c Refrigerant piping d Electrical wiring e Vinyl tape field supply f Power s...

Page 16: ...r 411 13 Piping installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 416 Onl...

Page 17: ...multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category...

Page 18: ...ndoor units 2 indoor units operates equally 2 1 3 P1 P2 P1 P2 P1 P2 2 1 3 1 2 3 e c d1 d2 b a a Power supply b Residual current device c Outdoor unit d Indoor unit e User interface Group control 1 rem...

Page 19: ...ing checklist Next to the commissioning instructions in this chapter a general commissioning checklist is also available on the Daikin Business Portal authentication required The general commissioning...

Page 20: ...thermostat OFF at cooling operation LL 2 12 22 6 01 Setup volume 2 02 OFF 03 Monitoring 1 2 04 Monitoring 3 2 05 During thermostat OFF at heating operation LL 2 12 22 3 01 Setup volume 2 02 OFF 03 Mon...

Page 21: ...a Input OFF ON Result turns the unit ON Input OFF enables control by user interface a Input ON OFF Result Turns the unit OFF How to select FORCED OFF and ON OFF OPERATION 1 Turn on the power and then...

Page 22: ...y PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R...

Page 23: ......

Page 24: ...3P654518 1A 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: