17 Configuration

Installation and operation manual

20

FAA71+100BUV1B

Split system air conditioner

3P654518-1A – 2021.03

16.2

To perform a test run

INFORMATION

For the test run procedure, see the reference guide or the
service manual of the used user interface.

NOTICE

Do NOT interrupt the test run.

17

Configuration

17.1

Field setting

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Airflow rate increase mode

▪ Airflow rate when thermostat control is OFF

▪ Time to clean air filter

▪ Indoor unit number of simultaneous operation system

▪ Simultaneous operation system individual setting

▪ Computerised control (forced OFF and ON/OFF operation)

INFORMATION

▪ The  connection  of  optional  accessories  to  the  indoor

unit  might  cause  changes  to  some  field  settings.  For
more  information,  see  the  installation  manual  of  the
optional accessory.

▪ Following  setting  are  only  applicable  when  using  the

BRC1H52*  user  interface.  When  using  any  other  user
interface, see the installation manual or service manual
of the user interface.

Setting: Airflow rate increase mode

This  setting  must  correspond  with  the  needs  of  the  user.  It  is
possible  to  raise  set  airflow  (HIGH,  MEDIUM  and  LOW)  from  the
field. Change the value number (—) as shown in the table below.

If you want airflow…

Then

(1)

M

SW

Standard

13 (23)

0

01

A little increased

02

Increased

03

Setting: Airflow rate when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the airflow rate speed:

If you want…

Then

(1)

M

SW

Fan operation
during thermostat
OFF (cooling/
heating operation)

Normal

11 (21)

2

01

Stop

02

During thermostat
OFF at cooling
operation

LL

(2)

12 (22)

6

01

Setup volume

(2)

02

OFF

03

Monitoring 1

(2)

04

Monitoring 3

(2)

05

During thermostat
OFF at heating
operation

LL

(2)

12 (22)

3

01

Setup volume

(2)

02

OFF

03

Monitoring 1

(2)

04

Monitoring 2

(2)

05

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which 

"Time to clean filter"

 notification

is displayed on the user interface.

If you want an interval of…

(air contamination)

Then

(1)

M

SW

±200 h (light)

10 (20)

0

01

±100 h (heavy)

02

Setting: Indoor unit number of simultaneous operation system

For  simultaneous  operation  system  mode  made  following  field
setting:

If the system mode is…

Then

(1)

M

SW

Pair (1 unit)

11 (21)

0

01

Simultaneous (2 units)

02

Simultaneous (3 units)

03

When  using  in 

simultaneous  operation

  system  mode,  refer  to

“simultaneous  operation  system  individual  setting”  section  to  set
master and slave units separately.

When  using 

wireless  remote  controllers,

  wireless  remote

controller  address  setting  is  necessary.  Refer  to  the  installation
manual  attached  to  the  wireless  remote  controller  for  setting
instructions.

Setting: Simultaneous operation system individual setting

Perform  the  following  procedure  when  setting  the  master  and  slave
unit separately.

1

Change setting:

If you want…

Then

(1)

M

SW

Unified setting

11 (21)

1

01

Individual setting

02

2

Perform field setting for the master unit.

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

SW

: Setting number

• —: Value number

: Default

(2)

Fan speed:

LL

: Low fan speed (set during thermostat OFF)

L

: Low fan speed (set by the user interface)

Setup volume

: The fan speed corresponds to the speed the user has set using the fan speed button on the user interface.

Monitoring 1, 2, 3

: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by 

LL

 (Monitoring 1), 

L

(Monitoring 2) or

 Setup volume 

(Monitoring 3).

Summary of Contents for FAA-B

Page 1: ...Installation and operation manual Split system air conditioner English Installation and operation manual Split system air conditioner FAA71BUV1B FAA100BUV1B...

Page 2: ...na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus normi...

Page 3: ...to the indoor unit 17 15 Finishing the indoor unit installation 19 15 1 To fix the unit on the mounting plate 19 16 Commissioning 19 16 1 Checklist before commissioning 19 16 2 To perform a test run 2...

Page 4: ...ay cause refrigerant gas leakage CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refri...

Page 5: ...nd human health For more information contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household was...

Page 6: ...ION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch before executing any maintenance task CAUTION Do NOT insert fingers rods o...

Page 7: ...ing unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electric shock or fire Contact your dealer 4 About the system WARNING Do NOT modify disassemb...

Page 8: ...40 Outdoor temperature 15 46 C DB 15 15 5 C WB Indoor temperature 14 28 C WB 10 27 C DB Indoor humidity 80 a a To avoid condensation and water dripping out of the unit If the temperature or the humidi...

Page 9: ...on as desired What The system directs the airflow differently depending on the user selection CAUTION ALWAYS use a user interface to adjust the angle of the flap When the flap is swinging and you move...

Page 10: ...terminals of main circuit capacitors or electrical components before servicing 7 2 Cleaning the unit CAUTION Turn off the unit before cleaning the air outlet exterior front panel and air filter 7 2 1...

Page 11: ...e of the refrigerant total refrigerant charge in kg 1000 Please contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly f...

Page 12: ...of the carrier Bring the packed unit as close as possible to its final installation position to prevent damage during transport Unpack the indoor unit completely according to the instructions mention...

Page 13: ...ting plate 1 Remove the mounting plate from the unit Remove 2 screws from class 71 or 1 screw from class 100 Push the knobs in the direction of the arrow Remove the mounting plate A b a b 1 1 c 2 c 2...

Page 14: ...ary fixing hole 12 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electr...

Page 15: ...trical wiring and the refrigerant pipes together using vinyl tape field supply c e f b d a A A c g a Drain hose b Wall hole c Refrigerant piping d Electrical wiring e Vinyl tape field supply f Power s...

Page 16: ...r 411 13 Piping installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 416 Onl...

Page 17: ...multicore cable for power supply cables WARNING Use an all pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full disconnection under overvoltage category...

Page 18: ...ndoor units 2 indoor units operates equally 2 1 3 P1 P2 P1 P2 P1 P2 2 1 3 1 2 3 e c d1 d2 b a a Power supply b Residual current device c Outdoor unit d Indoor unit e User interface Group control 1 rem...

Page 19: ...ing checklist Next to the commissioning instructions in this chapter a general commissioning checklist is also available on the Daikin Business Portal authentication required The general commissioning...

Page 20: ...thermostat OFF at cooling operation LL 2 12 22 6 01 Setup volume 2 02 OFF 03 Monitoring 1 2 04 Monitoring 3 2 05 During thermostat OFF at heating operation LL 2 12 22 3 01 Setup volume 2 02 OFF 03 Mon...

Page 21: ...a Input OFF ON Result turns the unit ON Input OFF enables control by user interface a Input ON OFF Result Turns the unit OFF How to select FORCED OFF and ON OFF OPERATION 1 Turn on the power and then...

Page 22: ...y PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R...

Page 23: ......

Page 24: ...3P654518 1A 2021 03 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: