8 Commissioning
Installation manual
22
EZESHP20 EZLSHP20AUAW1B
Exigo E1500 Trailer Refrigeration Unit
4P726857-1 – 2023.03
1
Install the pre-filter heater (c).
2
Guide the electrical cable from the pre-filter to the unit.
3
Plug the 2 pin connector of the connection cable in the socket
of the unit cable.
The pre-filter heater cable is connected to the X60Y connector.
INFORMATION
Full installation instructions are delivered with the option
kit.
7.12
To install the solar panel
a
b
a
Solar panel
b
Charge controller
1
Install the solar panel (a).
The door solar panel cable is connected to the battery poles.
INFORMATION
Full installation instructions are delivered with the option
kit.
8
Commissioning
CAUTION
Preliminary electrical system checks such as earth
continuity, polarity, resistance to earth and short circuit
must be carried out by using a suitable test meter by a
competent person.
WARNING
ONLY qualified persons should conduct commissioning.
Final checks
The following checks must be performed before handing the cold
room with the installed unit over to the user:
1
Check all fluid components and connections inside the unit.
Make sure they are not damaged during installation and that
there are no visible leakages.
2
Check that all auxiliary components are installed correctly and
that there are no visible leakages:
▪ Fuel tank
▪ Fuel pre-filter
▪ Fuel pump
▪ Fuel lines and connections
WARNING
If diesel leaks from the fuel system, it evaporates. These
vapors are irritating to eyes, respiratory system and skin
and can ignite if an open flame is in the area.
3
Check that there is no air gap between unit and cold room wall.
4
Check that the exhaust pipe can discharge optimally.
5
Check that all covers can be closed correctly.
Test run
After installation the installer is obliged to verify the correct operation
of the unit. Therefore a test run MUST be performed according to the
procedures described below.
WARNING
▪ NEVER
directly
touch
any
accidental
leaking
refrigerant. This could result in severe wounds caused
by frostbite.
▪ Do NOT touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.