Safety 

The unit must be firmly secured to the soil. 
It is essential to observe the following instructions: 

 

The unit can only be lifted using the  lifting points marked 
in yellow fixed to its base.  

 

It is forbidden to access the electrical components without 
having  opened  the  unit main switch  and  switched  off the 
power supply. 

 

It is forbidden to access the electrical components without 
using an insulating platform. Do not access the electrical 
components if water and/or moisture are present. 

 

Sharp  edges  and  the  surface  of  the  condenser  section 
could cause injury. Avoid direct contact and use adeguate 
protection device 

 

Switch  off  power  supply,  by  opening  the  main  switch, 
before  servicing  the  cooling  fans  and/or  compressors. 
Failure  to  observe  this  rule  could  result  in  serious 
personal injury. 

 

Do  not  introduce  solid  objects  into  the  water  pipes  while 
the unit is connected to the system. 

 

A  mechanical  filter  must  be  installed  on  the  water  pipe 
connected to the heat exchanger inlet. 

 

The  unit  is  supplied  with  safety  valves,  that  are  installed 
both on the high-pressure and on the low-pressure sides 
of the refrigerant circuit. 

It  is  absolutely  forbidden  to  remove  all  protections  of 
moving parts. 

 
In case of sudden stop of the unit, follow the instructions on the 

Control  Panel  Operating  Manual

  which  is  part  of  the  on-

board documentation delivered to the end user. 
 
It  is  strongly  recommended  to  perform  installation  and 
maintenance with other people. In case of accidental injury or 
unease, it is necessary to: 

-

 

keep calm 

-

 

press the alarm button if present in the installation site 

-

 

move the injured person in a warm place far from the unit 
and in rest position 

-

 

contact  immediately  emergency  rescue  personnel  of  the 
building or the Health Emergency Service 

-

 

wait  without  leaving  the  injured  person  alone  until  the 
rescue operators come 

-

 

give all necessary information to the  rescue operators 

 

Avoid  installing  the  chiller  in  areas  that  could  be 
dangerous  during  maintenance  operations,  such  as 
platforms  without  parapets  or  railings  or  areas  not 
complying  with  the  clearance  requirements  around  the 
chiller. 

 
Noise 

The  unit  is  a  source  of  noise  mainly  due  to  rotation  of 
compressors and fans. 
The  noise  level  for  each  model  size  is  listed  in  sales 
documentation. 
If  the  unit  is  correctly  installed,  operated  and  manteined  the 
noise  emission  level  do  not  require  any  special  protection 
device to operate continuosly close to the unit without any risk. 
In  case  of  installation  with  special  noise  requirements  it  could 
be necessary to install additional sound attenuation devices. 

 
Moving and lifting 

Avoid  bumping  and/or  jolting  during  loading/unloading  unit 
from the truck and moving it. Do not push or pull the unit from 
any part other than the base frame. Secure the unit inside the 
truck to prevent it from moving and causing  damages. Do not 
allow  any  part  of  the  unit  to  fall  during  transportation  or 
loading/unloading. 
All units of the series are supplied with lifting points marked in 
yellow.  Only  these  points  may  be  used  for  lifting  the  unit,  as 
shown in the following figure. 
Use  spacing  bars  to  prevent  damage  to  the  condensation 
bank.  Position  these  above  the  fan  grills  at  a  distance  of  at 

least 2.5 metres

 

Both  the  lifting  ropes  and  the  spacing  bars  must  be 
strong  enough  to  support  the  unit  safely.  Please  check 
the unit’s weight on the unit nameplate.  

The  unit  must  be  lifted  with  the  utmost  attention  and  care 
following lifting label instructions; lift unit very slowly, keeping it 
perfectly level. 
 

Positioning and assembly 

All  units  are  designed  for  installation  outdoors,  either  on 
balconies or on the ground, provided that the installation area 
is  free  of  obstacles  that  could  reduce  air  flow  to  the 
condensers coil. 
The  unit  must  be  installed  on  a  robust  and  perfectly  level 
foundation; should the unit be installed on balconies or roofs, it 
might be necessary to use weight distribution beams. 

 

Figure 2 - Lifting 

Unit with 4 lifting points 

(The drawing shows only the 6 fans version. For the 4 fans version the lifting mode is the same) 

 

 

Summary of Contents for EWAD TZ

Page 1: ...nverter Installation Operation and Maintenance Manual Air cooled chiller with inverter driven screw compressor EWAD TZ Refrigerant R 134a Original Instructions Installation Operation and Maintenance M...

Page 2: ...D EIMAC00907 16EN 2 20 A Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 3: ...D EIMAC00907 16EN 3 20 B Typical refrigerant circuit with heat recovery Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 4: ...isolating valve 16 SAE Flare valve 17 Evaporator water inlet connection 18 Evaporator water outlet connection 19 2 Way charging valve 20 Heat Recovery Optional 21 Heat Recovery water outlet connectio...

Page 5: ...nance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reaching final place of installation All comp...

Page 6: ...the electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7...

Page 7: ...the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or railings or areas not complying with the clearance requirements around the chiller Nois...

Page 8: ...s be avoided In case the AVM s are not adjustable spring type are normally not adjustable the flatness of the unit frame must be guaranteed by using metal plate spacers Before unit commissioning the f...

Page 9: ...for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstacles of the same height...

Page 10: ...uit on the right is working quite normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figur...

Page 11: ...e water system the Installer has to guarantee the cleaning of the water pipes between the water filter and the evaporator 9 Evaporator has an electrical resistance with a thermostat that ensures prote...

Page 12: ...an be installed either on the inlet or outlet water piping The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the evaporator from freezing The ma...

Page 13: ...of all the safety devices During the unit s initial start up phase a technician authorized by the manufacturer is available to answer any questions and to give instructions as to the correct operating...

Page 14: ...enance Plan for Critical Application and or Highly Aggressive Environment List of Activities Note 8 Weekly Monthly Note 1 Yearly Seas Onal Note 2 General Reading of operating data Note 3 X Visual insp...

Page 15: ...old bleach or acid cleaners should not be used to clean E coated coils These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the E coating If there is d...

Page 16: ...refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislat...

Page 17: ...D EIMAC00907 16EN 17 20...

Page 18: ...D EIMAC00907 16EN 18 20...

Page 19: ...D EIMAC00907 16EN 19 20...

Page 20: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...