 D-EIMAC00907-16EN - 16/20 

 

 

5. 

The  water  used  for  filling  the  water  circuit must  be  clean 
and suitably treated. A mechanical filter must be installed 
at the point closest to the evaporator inlet. 

6. 

Unless  there  is  a  specific  agreement  at  the  time  of 
ordering,  the  evaporator  water  flow  rate  must  never  be 
above 120% and below 80% of the nominal flow rate. 

 

Periodic obligatory checks and starting up of 
appliances under pressure  

The  units  are  included  in category 

I →  III  of the classification 

established by the European Directive 2014/68/EU (PED).  
For chillers belonging to this category, some local regulations 
require a periodic inspection by an authorized agency. Please 
check with your local requirements.

 

Important information regarding the refrigerant 
used  

This  product  contains  fluorinated  greenhouse  gases.  Do  not 
vent gases into the atmosphere. 
Refrigerant type: 

 

R134a 

GWP(1) value: 

 

1300 

(1)GWP = 

 

global warming potential 

 
The  refrigerant  quantity  necessary  for  standard  operation  is 
indicated on the unit name plate. 
Real refrigerant quantity charged in the unit is listed on a silver 
sticker inside the electrical panel. 
Periodical  inspections  for  refrigerant  leaks  may  be  required 
depending on European or local legislation. 
Please contact your local dealer for more information. 

Disposal 

The  unit  is  made  of  metal,  plastic  and  electronic  parts.    All 
these  parts  must  be  disposed  of  in  accordance  with  the  local 
regulations in terms of disposal. 
Lead  batteries  must  be  collected  and  sent  to  specific  refuse 
collection centres.  
Oil  must  be  collected  and  sent  to  specific  refuse  collection 
centres.  

 

 

 

 

This manual is a technical aid and does not represent a binding offer. The content cannot be held as explicitly or implicitly guaranteed  as complete, precise or reliable. All data and 
specifications contained herein may be modified without notice. The data communicated at the moment of the order shall hold firm. 
The manufacturer shall assume no liability whatsoever for any direct or indirect damage, in the widest sense of the term, ensuing from or connected with the use and/or interpretation 
of this manual. 
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for EWAD TZ

Page 1: ...nverter Installation Operation and Maintenance Manual Air cooled chiller with inverter driven screw compressor EWAD TZ Refrigerant R 134a Original Instructions Installation Operation and Maintenance M...

Page 2: ...D EIMAC00907 16EN 2 20 A Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 3: ...D EIMAC00907 16EN 3 20 B Typical refrigerant circuit with heat recovery Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 4: ...isolating valve 16 SAE Flare valve 17 Evaporator water inlet connection 18 Evaporator water outlet connection 19 2 Way charging valve 20 Heat Recovery Optional 21 Heat Recovery water outlet connectio...

Page 5: ...nance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reaching final place of installation All comp...

Page 6: ...the electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7...

Page 7: ...the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or railings or areas not complying with the clearance requirements around the chiller Nois...

Page 8: ...s be avoided In case the AVM s are not adjustable spring type are normally not adjustable the flatness of the unit frame must be guaranteed by using metal plate spacers Before unit commissioning the f...

Page 9: ...for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstacles of the same height...

Page 10: ...uit on the right is working quite normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figur...

Page 11: ...e water system the Installer has to guarantee the cleaning of the water pipes between the water filter and the evaporator 9 Evaporator has an electrical resistance with a thermostat that ensures prote...

Page 12: ...an be installed either on the inlet or outlet water piping The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the evaporator from freezing The ma...

Page 13: ...of all the safety devices During the unit s initial start up phase a technician authorized by the manufacturer is available to answer any questions and to give instructions as to the correct operating...

Page 14: ...enance Plan for Critical Application and or Highly Aggressive Environment List of Activities Note 8 Weekly Monthly Note 1 Yearly Seas Onal Note 2 General Reading of operating data Note 3 X Visual insp...

Page 15: ...old bleach or acid cleaners should not be used to clean E coated coils These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the E coating If there is d...

Page 16: ...refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislat...

Page 17: ...D EIMAC00907 16EN 17 20...

Page 18: ...D EIMAC00907 16EN 18 20...

Page 19: ...D EIMAC00907 16EN 19 20...

Page 20: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: