background image

  D

–EIMAC00907–16EN - 15/20 

Unit Maintenance and Cleaning 

Unit  exposed  to  a  highly  aggressive  environment  can  face 
corrosion  in  a  shorter  time  than  ones  installed  on  a  standard 
environment.  Corrosion  causes  a  rapid  rusting  of  the  frame 
core, consequently decreases unit structure life time. To avoid 
that,  it  is  necessary  to  wash  periodically  the  frame  surfaces 
with water and suitable detergents. 
In  case  of  part  of  unit  frame  paint  came  off,  it  is  important  to 
stop  its  progressive  deterioration  by  repainting  the  exposed 
parts  using  proper  products.  Please  contact  factory  to  get  the 
required products specifications. 
 
Note:  in case  of  just salt  deposits  are  present,  it is  enough  to 
rinse the parts with fresh water. 

 
Microchannel Coil Maintenance 

Routine  cleaning  of  coil  surfaces  is  essential  to  maintain 
proper  operation  of  the  unit,  avoid  corrosion  and  rusting. 
Elimination  of  contamination  and  removal  of  harmful  residues 
will greatly increase the life of the coil and extend the life of the 
unit. 
Relative  to  fin  and  tube  heat  exchangers,  microchannel  coils 
tend  to  accumulate more  of  the  dirt  on  the  surface  and  of  the 
less dirt inside which can make them easier to clean. 
The  following  maintenance  and  cleaning  procedure  are 
recommended as part of the routine maintenance activities. 
 
1. 

Remove  surface  dirt,  leaves,  fibers,  etc.  with  a  vacuum 
cleaner  (preferably  with  a  brush  or  other  soft  attachment 
rather than a metal tube), compressed air blown from the 
inside  out,  and/or  a  soft  bristle  (not  wire!)  brush.  Do  not 
impact  or  scrape  the  coil  with  the  vacuum  tube,  air 
nozzle, etc.. 

NOTE: Use of a water stream, such as a garden hose, against 
a surface loaded coil will drive the fibers and dirt into the coil. 
This  will  make  cleaning  efforts  more  difficult.  Surface  loaded 
fibers  must  be  completely  removed  prior  to  using  low  velocity 
clean water rinse. 
 
2. 

Rinse.  Do  not  use  any  chemicals  (including  those 
advertised  as  coil  cleaners)  to  wash  microchannel  heat 
exchangers. They can cause corrosion. Rinse only. Hose 
the  MCHE  off  gently,  preferably  from  the  inside  out  and 
top  to  bottom,  running  the  water  through  every  fin 
passage  until  it  comes  out  clean.  Microchannels  fins  are 
stronger than traditional tube & fin coil fins but still need to 
be handled with care. 

 

It  is  possible  to clean  a coil  with  a  high  pressure  washer 
(max  62  barg)  only  if  a  flat  shape  of  the  water  spray  is 
used and direction of the spay is kept perpendicular to the 
fin edge. 

If this direction is not respected the coil may 

be  destroyed 

if  using  a  pressure  washer  so  we  do  not 

recommend their use.

 

NOTE: A monthly clean  water  rinse  is  recommended  for  coils 
that are applied in coastal or industrial environments to help to 
remove  chlorides,  dirt  and  debris.  It  is  very  important  when 
rinsing,  to  water  temperature  is  less  than  550.  An  elevated 
water  temperature  (not  to  exceed  550  C)  will  reduce  surface 
tension, increasing the ability to remove chlorides and dirt. 
 
3. 

Quarterly  cleaning  is  essential  to extend  the  life  of  an  E-
coated coil and is required to maintain warranty coverage. 
Failure  to  clean  an  E-coated  coil  will  void  the  warranty 
and may result in reduced efficiency and durability in the 
environment. For routine quarterly cleaning, first clean the 
coil with an approved coil cleaner. After cleaning the coils 
with  the  approved  cleaning  agent,  use  the  approved 
chloride  remover  to  remove  soluble  salts  and  revitalize 
the unit. 

NOTE:  Harsh  chemicals,  household  bleach  or  acid  cleaners 
should  not  be  used  to  clean  E-coated  coils.  These  cleaners 
can be very difficult to rinse out of the coil and can accelerate 
corrosion  and  attack  the  E-coating.  If  there  is  dirt  below  the 
surface  of  the  coil,  use  the  recommended  coil  cleaners  as 
described above. 

 
Inverter Electrolytic Capacitors 

Compressor  Inverters  include  electrolytic  capacitors  which 
have  been  designed  to  last  a  minimum  of  15  years  in  normal 
use.  Heavy  duty  conditions  may  reduce  the  actual  life  of 
capacitors. 
The  chiller  calculates  capacitor  residual  life  based  on  actual 
operation.  When  residual  life  gets  below  a  give  threshold,  a 
warning is issued by the controller. In this case replacement of 
capacitors is recommended.  This operation must be done only 
by  qualified  technicians.  Replacement  must  be  carried  out 
through the following procedure: 

 

Power off the chiller 

 

Wait for 5 minutes before opening the inverter case 

 

Check that residual dc voltage in the dc link is zero. 

 

Open  the  inverter  case  and  replace  old  capacitors 
with new ones. 

 

Reset the chiller controller through the maintenance 
menu. This will allow the controller to recalculate the 
new estimated life of the capacitors. 

 

Capacitor Reforming after long shut-off period 

Electrolytic  capacitors  may  lose  part  of  their  original 
characteristics if they are not powered for more than 1 year. If 
chiller  has  been  shut  off  for  a  longer  period  a  “reforming” 
procedure as follows is necessary: 

 

Power on the inverter 

 

Keep it powered on  without starting the compressor 
for at least 30 minutes 

 

After 30 minutes the compressor can be started 

 
Low Ambient Start-up 

Inverters  include  a  temperature  control  which  allows  them  to 
withstand ambient temperatures down to -20°C. However they 
should  not  be  switched  on  at  temperatures  lower  than  0°C 
unless the following procedure is executed: 

 

Open the switchbox (only trained technicians should 
perform this operation) 

 

Open compressor fuses (by pulling the fuse holders) 
or compressor circuit breakers 

 

Power on the chiller 

 

Keep the chiller powered on for 1 hour at least (this 
allows inverter heaters to warm-up the inverter). 

 

Close fuse holders 

 

Close the switchbox 

 

Service and limited warranty 

All units are factory-tested and guaranteed for 12 months as of 
the first start-up or 18 months as of delivery. 
These  units  have  been  developed  and  constructed  according 
to  high  quality  standards  ensuring  years  of  failure-free 
operation.  It  is  important,  however,  to  ensure  proper  and 
periodical  maintenance  in  accordance  with  all  the  procedures 
listed  in  this  manual  and  with  good  practice  of  machines 
maintenance.  
We  strongly  advise  stipulating  a  maintenance  contract  with  a 
service  authorized  by  the  manufacturer  in  order  to  ensure 
efficient and problem-free service, thanks to the expertise and 
experience of our personnel. 
It  must  also  be  taken  into  consideration  that  the  unit  requires 
maintenance also during the warranty period.

 

It  must  be  borne  in  mind  that  operating  the  unit  in  an 
inappropriate  manner,  beyond  its  operating  limits  or  not 
performing  proper  maintenance  according  to  this  manual  can 
void the warranty. 
Observe  the  following  points  in  particular,  in  order  to  conform 
to warranty limits: 
1. 

The unit cannot function beyond the specified limits  

2. 

The  electrical  power  supply  must  be  within  the  voltage 
limits and without voltage harmonics or sudden changes. 

3. 

The  three-phase  power  supply  must  not  have  un 
unbalance between phases exceeding 3%. The unit must 
stay  turned  off  until  the  electrical  problem  has  been 
solved. 

4. 

No  safety  device,  either  mechanical,  electrical  or 
electronic must be disabled or overridden. 

Summary of Contents for EWAD TZ

Page 1: ...nverter Installation Operation and Maintenance Manual Air cooled chiller with inverter driven screw compressor EWAD TZ Refrigerant R 134a Original Instructions Installation Operation and Maintenance M...

Page 2: ...D EIMAC00907 16EN 2 20 A Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 3: ...D EIMAC00907 16EN 3 20 B Typical refrigerant circuit with heat recovery Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 4: ...isolating valve 16 SAE Flare valve 17 Evaporator water inlet connection 18 Evaporator water outlet connection 19 2 Way charging valve 20 Heat Recovery Optional 21 Heat Recovery water outlet connectio...

Page 5: ...nance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reaching final place of installation All comp...

Page 6: ...the electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7...

Page 7: ...the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or railings or areas not complying with the clearance requirements around the chiller Nois...

Page 8: ...s be avoided In case the AVM s are not adjustable spring type are normally not adjustable the flatness of the unit frame must be guaranteed by using metal plate spacers Before unit commissioning the f...

Page 9: ...for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstacles of the same height...

Page 10: ...uit on the right is working quite normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figur...

Page 11: ...e water system the Installer has to guarantee the cleaning of the water pipes between the water filter and the evaporator 9 Evaporator has an electrical resistance with a thermostat that ensures prote...

Page 12: ...an be installed either on the inlet or outlet water piping The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the evaporator from freezing The ma...

Page 13: ...of all the safety devices During the unit s initial start up phase a technician authorized by the manufacturer is available to answer any questions and to give instructions as to the correct operating...

Page 14: ...enance Plan for Critical Application and or Highly Aggressive Environment List of Activities Note 8 Weekly Monthly Note 1 Yearly Seas Onal Note 2 General Reading of operating data Note 3 X Visual insp...

Page 15: ...old bleach or acid cleaners should not be used to clean E coated coils These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the E coating If there is d...

Page 16: ...refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislat...

Page 17: ...D EIMAC00907 16EN 17 20...

Page 18: ...D EIMAC00907 16EN 18 20...

Page 19: ...D EIMAC00907 16EN 19 20...

Page 20: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: