background image

  D

–EIMAC00907–16EN - 12/20 

 
Evaporator 

and 

recovery 

exchangers 

anti-freeze 

protection 

All  evaporators  are  supplied  with  a  thermostatically  controlled 
anti-freeze electrical resistance, which provides adequate anti-
freeze protection at temperatures as low as 

–25°C.  

However,  unless  the  heat  exchangers  are  completely  empty 
and  cleaned  with  anti-freeze  solution,  additional  methods 
should also be used against freezing. 
Two  or  more  of  below  protection  methods  should  be 
considered when designing the system as a whole: 

 

Continuous  water  flow  circulation  inside  piping  and 
exchangers 

 

Addition  of  an  appropriate  amount  of  glycol  inside  the 
water circuit 

 

Additional heat insulation and heating of exposed piping 

 

Emptying  and  cleaning  of  the  heat  exchanger  during  the 
winter season 

It  is  the  responsibility  of  the  installer  and/or  of  local 
maintenance  personnel  to  ensure  that  described  anti-freeze 
methods  are  used.  Make  sure  that  appropriate  anti-freeze 
protection  is  maintained  at  all  times.  Failing  to  follow  the 
instructions  above  could  result  in  unit  damage.  Damage 
caused by freezing is not covered by the warranty. 

 
Installing the flow switch 

To  ensure  sufficient  water  flow  through  the  evaporator,  it  is 
essential  that  a  flow  switch  be  installed  on  the  water  circuit. 

The  flow  switch  can  be  installed  either  on  the  inlet  or  outlet 
water piping. The purpose of the flow switch is to stop the unit 
in  the  event  of  interrupted  water  flow,  thus  protecting  the 
evaporator from freezing. 
The  manufacturer  offers,  as  optional,  a  flow  switch  that  has 
been selected for this purpose. 
This paddle-type flow switch is suitable for heavy-duty outdoor 
applications (IP67) and pipe diameters in the range of 1” to 6”. 
The flow switch is provided with a clean contact which must be 
electrically  connected  to  terminals  shown  in  the  wiring 
diagram. 
Flow  switch  has  to  be  tune  to  intervene  when  the  evaporator 
water flow is lower than 50% of nominal flow rate. 

 
Heat recovery 

Units may be optionally equipped with heat recovery system. 
This  system  in  made  by  a  water  cooled  heat  exchanger 
located  on  the  compressors  discharge  pipe  and  a  dedicated 
management of condensing pressure. 
To  guarantee  compressor  operation  within  its  envelope,  units 
with  heat  recovery  cannot  operate  with  water  temperature  of 
the heat recovery water lower than 28°C. 
It  is  a  responsibility  of  plant  designer  and  chiller  installer  to 
guarantee  the  respect  of  this  value  (e.g.  using  recirculating 
bypass valve) 
 

 

 

Figure 6 - Water piping connection for evaporator 

 

1. 

Pressure Gauge 

2. 

Flexible connector 

3. 

Flow switch 

4. 

Temperature probe 

5. 

Isolation Valve 

6. 

Pump 

7. 

Filter 

 
 

Figure 7 - Water piping connection for heat recovery exchangers 

 

1. 

Pressure Gauge 

2. 

Flexible connector 

3. 

Temperature probe 

4. 

Isolation Valve 

5. 

Pump 

6. 

Filter 

Summary of Contents for EWAD TZ

Page 1: ...nverter Installation Operation and Maintenance Manual Air cooled chiller with inverter driven screw compressor EWAD TZ Refrigerant R 134a Original Instructions Installation Operation and Maintenance M...

Page 2: ...D EIMAC00907 16EN 2 20 A Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 3: ...D EIMAC00907 16EN 3 20 B Typical refrigerant circuit with heat recovery Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 4: ...isolating valve 16 SAE Flare valve 17 Evaporator water inlet connection 18 Evaporator water outlet connection 19 2 Way charging valve 20 Heat Recovery Optional 21 Heat Recovery water outlet connectio...

Page 5: ...nance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reaching final place of installation All comp...

Page 6: ...the electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7...

Page 7: ...the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or railings or areas not complying with the clearance requirements around the chiller Nois...

Page 8: ...s be avoided In case the AVM s are not adjustable spring type are normally not adjustable the flatness of the unit frame must be guaranteed by using metal plate spacers Before unit commissioning the f...

Page 9: ...for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstacles of the same height...

Page 10: ...uit on the right is working quite normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figur...

Page 11: ...e water system the Installer has to guarantee the cleaning of the water pipes between the water filter and the evaporator 9 Evaporator has an electrical resistance with a thermostat that ensures prote...

Page 12: ...an be installed either on the inlet or outlet water piping The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the evaporator from freezing The ma...

Page 13: ...of all the safety devices During the unit s initial start up phase a technician authorized by the manufacturer is available to answer any questions and to give instructions as to the correct operating...

Page 14: ...enance Plan for Critical Application and or Highly Aggressive Environment List of Activities Note 8 Weekly Monthly Note 1 Yearly Seas Onal Note 2 General Reading of operating data Note 3 X Visual insp...

Page 15: ...old bleach or acid cleaners should not be used to clean E coated coils These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the E coating If there is d...

Page 16: ...refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislat...

Page 17: ...D EIMAC00907 16EN 17 20...

Page 18: ...D EIMAC00907 16EN 18 20...

Page 19: ...D EIMAC00907 16EN 19 20...

Page 20: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: