 D-EIMAC00907-16EN - 10/20 

 

 

 

 
 
The  minimum  distances,  reported  above,  ensure  functionality 
of the chiller in most applications. However, there are specific 
situations  which  include  multiple  chiller  installations:  in  this 
case the following recommendations are to be followed: 

 

Multiple  chiller  installed  side  by  side  in  a  free  field  with 
dominant wind. 

Considering an installation in areas with a dominant wind from 
a specific direction (as shown in the Fig.5): 

 

Chiller  N°1:  is  performing  normally  without  any 
ambient over-temperature  

 

Chiller  N°  2:  is  working  in  a  warmed  ambient.  The 
first  circuit  (from  the  left)  is  working  with  air 
recirculating from Chiller 1 and the second circuit to 
the  recirculating  air  from  the  chiller  N°1  and 
recirculation from itself.  

 

Chiller  N°  3:  circuit  on  the  left  is  working  in  a  over-
temperature ambient due to the recirculating air from 
the  other  two  chillers,  circuit  on  the  right  is  working 
quite normally. 

In  order  to  avoid  the  hot  air  recirculation  due  to  dominant 
winds,  the  installation  where  all  chillers  are  aligned  to  the 
dominant wind is preferred (see figure below): 
 

Multiple chiller installed side by side in a compound. 

In  case  of  compounds  with  walls  of  the  same  height  of  the 
chillers or higher, the installation is not recommended. Chiller 2 
and chiller 3 work with sensible higher temperature due to the 
enhanced  recirculation.  In  this  case  special  precautions  must 
be taken in to account according to the specific installation (eg: 
louvered  walls,  install  the  unit  on  base  frame  in  order  to 
increase the height, ducts on the discharge of the fans, high lift 
fans, etc). 
 
All the above cases are even more sensitive in case of design 
conditions close to the limits of the unit operating envelope. 
 
NOTE:  Daikin  cannot  be  considered  responsible  in  case  of 
malfunctions  generated  by  hot  air  recirculation  or  insufficient 
airflow  as  result  of  improper  installation  if  the  above 
recommendations are ignored. 
 

 

Figure 5 

– Multiple Chiller Installation 

 

 

 

Summary of Contents for EWAD TZ

Page 1: ...nverter Installation Operation and Maintenance Manual Air cooled chiller with inverter driven screw compressor EWAD TZ Refrigerant R 134a Original Instructions Installation Operation and Maintenance M...

Page 2: ...D EIMAC00907 16EN 2 20 A Typical refrigerant circuit Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 3: ...D EIMAC00907 16EN 3 20 B Typical refrigerant circuit with heat recovery Water inlet and outlet are indicative Please refer to the machine dimensional diagrams for exact water connections...

Page 4: ...isolating valve 16 SAE Flare valve 17 Evaporator water inlet connection 18 Evaporator water outlet connection 19 2 Way charging valve 20 Heat Recovery Optional 21 Heat Recovery water outlet connectio...

Page 5: ...nance of the unit without any risk to people animals and or objects Receiving the unit The unit must be inspected for any possible damage immediately upon reaching final place of installation All comp...

Page 6: ...the electrical panel Single circuit unit Double circuits unit Label Identification 1 Manufacturer s logo 5 Cable tightening warning 2 Gas type 6 Non flammable gas symbol 3 Hazardous Voltage warning 7...

Page 7: ...the chiller in areas that could be dangerous during maintenance operations such as platforms without parapets or railings or areas not complying with the clearance requirements around the chiller Nois...

Page 8: ...s be avoided In case the AVM s are not adjustable spring type are normally not adjustable the flatness of the unit frame must be guaranteed by using metal plate spacers Before unit commissioning the f...

Page 9: ...for post installation maintenance operations Figure 3 shows the minimum space required Vertical air discharge must not be obstructed If the unit is surrounded by walls or obstacles of the same height...

Page 10: ...uit on the right is working quite normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figur...

Page 11: ...e water system the Installer has to guarantee the cleaning of the water pipes between the water filter and the evaporator 9 Evaporator has an electrical resistance with a thermostat that ensures prote...

Page 12: ...an be installed either on the inlet or outlet water piping The purpose of the flow switch is to stop the unit in the event of interrupted water flow thus protecting the evaporator from freezing The ma...

Page 13: ...of all the safety devices During the unit s initial start up phase a technician authorized by the manufacturer is available to answer any questions and to give instructions as to the correct operating...

Page 14: ...enance Plan for Critical Application and or Highly Aggressive Environment List of Activities Note 8 Weekly Monthly Note 1 Yearly Seas Onal Note 2 General Reading of operating data Note 3 X Visual insp...

Page 15: ...old bleach or acid cleaners should not be used to clean E coated coils These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the E coating If there is d...

Page 16: ...refrigerant quantity charged in the unit is listed on a silver sticker inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislat...

Page 17: ...D EIMAC00907 16EN 17 20...

Page 18: ...D EIMAC00907 16EN 18 20...

Page 19: ...D EIMAC00907 16EN 19 20...

Page 20: ...of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S...

Reviews: