
7
|
Technical data
Service manual
97
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
7.6.2 Field settings: Outdoor unit
To reduce maximum sound levels
If the sound level CANNOT meet the local regulation (e.g. Netherlands), the
maximum sound level can be reduced by cutting J5 jumper on the main PCB of the
outdoor unit.
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
48].
1
Cut the J5 jumper on the main PCB of the outdoor unit.
RXJ20~35A
RXJ42+50A
Field setting
Sound level reduction
To be used at …
Cut J5 jumper
1 dB
Day
J5 ECONO mode
activated via remote
controller
2 dB
(a)
Night
(a)
If this field setting is done, the maximum sound level will be 2 dB lower than the maximum
sound level during normal night operation (unit without this field setting and with outdoor
unit quiet operation activated). So when this field setting is done on the unit, it is NOT
needed to activate the outdoor unit quiet operation to meet the local regulation.
INFORMATION
New setting may affect the performance of the unit.
draft – 22/04/2022 08:50