3
|
Troubleshooting
Service manual
42
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
Check
Detail
Check the installation conditions
(specified in the installation manual).
▪
Does the installed model has
sufficient capacity?
▪
Is there a short circuit air flow caused
by insufficient installation space?
Check the outdoor temperature.
▪
Heating operation cannot be used
when the outdoor temperature is
18°C WB or higher.
▪
Cooling operation cannot be used
when the outdoor temperature is
below −10°C DB.
3.6.4 Operating noise and vibrations
Check
Detail
Check the installation conditions
(specified in the installation manual).
▪
Use general vibration prevention
where needed.
▪
If the mounting wall is too thin, you
must use cushion material or rubber,
or change the installation place.
▪
Refrigerant piping is too short; is the
length within specified range?
▪
Due to bad installation or general
conditions there may be deformation
of the unit.
▪
Are all the screws installed and
tightened properly?
▪
Is all piping secured, fixed and
supported by inserting a cushion
material where needed?
▪
Install piping weights or correct by
hand if any piping is in contact with
other parts.
▪
Is the fan in contact with other parts?
If so separate the fan from the other
parts.
Check refrigerant charge.
▪
Is the unit filled with the specified
refrigerant volume?
▪
Is there a flushing noise, due to
refrigerant shortage?
▪
Is there air in the system?
Check the expansion valve.
If a passing sound is heard from the
pressure reducing valve, apply sound
insulation sheets of putty to reduce the
valve noise.
draft – 22/04/2022 08:50