3
|
Troubleshooting
Service manual
22
RXJ20~50A + FTXJ-A(W)(S)(B)
Split Emura 3 R32
ESIE22-04 – 2022.04
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.5.12 E6-00 – Outdoor unit: Compressor startup defect
Trigger
Effect
Reset
The motor rotor does
NOT rotate when the
compressor is energized.
Unit will NOT stop
operating.
Automatic reset after a
continuous run for
10 minutes.
Unit will stop operating
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the discharge pipe thermistor. See Thermistors.
Possible cause:
Faulty discharge pipe thermistor or connector fault.
2
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
3
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
4
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge or shortage.
5
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
62].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
6
Perform a check of the compressor. See Compressor.
Possible cause:
Faulty compressor or miswiring of the compressor power
supply cable.
7
Perform a check of the main PCB. See Main PCB.
Possible cause:
Faulty main PCB.
8
Perform a check of the 4‑way valve. See 4-way valve.
Possible cause:
Faulty 4‑way valve.
9
Perform a check of the expansion valve. See Expansion valve.
Possible cause:
Faulty expansion valve.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.