31
31
EnglishEnglish
SYSteM SetUP (SYS SetUP1 and SYS SetUP2)
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
Reset System Setup Options to
Factory Defaults (SYS SETUP
RESET)
NO or YES
Selecting “YES” resets this menu to factory de-
fault settings.
SET MAX CURRENT
N/A
Future use.
VERTICAL RISE
Same Level, Outdoor Lower, or
Indoor Lower
If the outdoor & indoor units are /- 15 ft.
vertical distance, select “SAME LEVEL”. If the out-
door unit is more than 15 ft. below the indoor unit,
select “OUTDOOR LOWER”. If the outdoor unit
is more than 15 ft. above the indoor unit, select
“INDOOR LOWER”.
BOOST MODE (“BOOST MD”)
ON or OFF
“BOOST MD” turns BOOST MODE OFF or ON.
BOOST MODE is ON by default. See BOOST
MODE section of this manual for more details.
BOOST MODE TEMPERATURE
(BOOST TEMP)
Always ON, 70, 75, 80, 85, 90,
95, 100, 105°F
BOOST TEMP adjusts the activation temperature
from 70°F to 105°F. An “Always ON” option is also
available to permanently engage BOOST MODE.
NIGHT MODE (NIGHT MD)
(In case of CTK04)
ON or OFF
NIGHT MODE is OFF by default. See NIGHT
MODE section of this manual for more details.
NOISE DOWN LEVEL
1, 2, or 3
NOISE DOWN LEVEL adjusts the noise level. 3 is
the most quiet level.
NIGHT MODE START
(In case of CTK04)
-2Hour, -1Hour, Standard,
+1Hour, +2Hour
NIGHT MODE START adjusts the time to start for
NIGHT MODE.
NIGHT MODE END
(In case of CTK04)
-2Hour, -1Hour, Standard,
+1Hour, +2Hour
NIGHT MODE END adjusts the time to end for
NIGHT MODE.
CAPACITY PRIORITY
(CAP PRIORITY)
ON or OFF
CAP PRIORITY is ON by default. If during operation
the capacity demand is high, then the night mode
function will be temporarily overridden by the cap
priority function to return the room temperature to
the set point.
CHARGE MODE
ON or OFF
Enter Charging Mode. This allows for a steady
system operation for a duration of approximately
1 hour to allow for refrigerant charging of the sys-
tem via the suction charge port. The system will
stop after completion.
eQUiPMent teSt (eQUiP teSt)
SUBMENU ITEM
INDICATION/USER MODIFIABLE
OPTIONS
COMMENTS
System Verification Test
(SYSTEM TEST)
ON or OFF
System Verification Test must be run after installa
-
tion. This is approximately a 10-15 minute test. If
the thermostat is set to COOL mode, the system
will enter CHARGE mode upon completion, other-
wise it will stop.