![background image](http://html1.mh-extra.com/html/daikin/dsg-series/dsg-series_installation-instructions-manual_2460485032.webp)
32
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HIGH STATIC HORIZONTAL
DSG036 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
0.7
0.8
1269 0.45
0.9
1150 0.44
1.0
1225 0.48 988 0.40
1.1
1280 0.55 1063 0.44 824 0.37
1.2
1143 0.52 867 0.40
1.3
1268 0.59 963 0.48 651 0.36
1.4
1332 0.68 1127 0.55 766 0.43
1.5
1198 0.64 986 0.52
1.6
1304 0.74 1013 0.59 833 0.48
1.7
1165 0.69 828 0.54
1.8
1075 0.67
DSG048 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
1669 0.53
0.7
1741 0.61 1553 0.51
0.8
1792 0.66 1610 0.57 1408 0.48
0.9
1680 0.63 1479 0.53 1264 0.44
1
1765 0.71 1568 0.59 1323 0.50 1093 0.41
1.1
1640 0.67 1422 0.55 1168 0.46
1.2
1784 0.78 1515 0.64 1259 0.51 995 0.43
1.3
1821 0.89 1621 0.73 1360 0.59 1091 0.47
1.4
1694 0.84 1458 0.68 1202 0.55
1.5
1567 0.80 1324 0.63 1042 0.51
1.6
1417 0.75 1148 0.59
1.7
1262 0.70
1.8
1120 0.66
DSG060 HIGH STATIC BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2164 0.89 1985 0.76
0.7
2232 0.99 2047 0.85 1858 0.72
0.8
2104 0.95 1943 0.82 1735 0.70
0.9
2200 1.09 1995 0.92 1819 0.79 1603 0.67
1.0
2297 1.22 2086 1.06 1900 0.89 1687 0.75 1410 0.62
1.1
2204 1.19 1995 1.02 1774 0.86 1543 0.71
1.2
2249 1.32 2101 1.15 1875 0.99 1624 0.81 1352 0.66
1.3
2175 1.28 1958 1.11 1740 0.94 1482 0.77
1.4
2072 1.25 1836 1.06 1587 0.89 1308 0.72
1.5
1945 1.20 1685 1.00 1402 0.83
1.6
1841 1.15 1519 0.94
1.7
1684 1.09
1.8
1541 1.03
NOTE
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
Tables represent dry coil without filter, to compensate for filter add 0.08" to
measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5