30
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HIGH STATIC DOWN SHOT
DSG036 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
0.7
1222 0.40
0.8
1117 0.39
0.9
1221 0.46 1012 0.38
1.0
1246 0.52 1078 0.42 869 0.35
1.1
1126 0.49 935 0.39 725 0.33
1.2
1268 0.56 1006 0.46 763 0.36
1.3
1335 0.65 1141 0.53 847 0.42
1.4
1212 0.62 1014 0.5
690 0.38
1.5
1314 0.72 1090 0.58 887 0.47
1.6
1187 0.67 922 0.53 750 0.43
1.7
1060 0.63 753 0.49
1.8
978 0.61
DSG048 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
1688 0.58 1503 0.48
0.7
1716 0.62 1569 0.55 1398 0.46
0.8
1613 0.59 1450 0.51 1268 0.43
0.9
1702 0.67 1510 0.56 1331 0.48 1138 0.40
1.0
1589 0.64 1412 0.53 1190 0.45 984 0.37
1.1
1751 0.75 1477 0.60 1281 0.50 1052 0.42
1.2
1755 0.85 1605 0.70 1364 0.57 1133 0.46
1.3
1640 0.80 1459 0.66 1224 0.53 983 0.43
1.4
1525 0.76 1313 0.61 1083 0.49
1.5
1410 0.72 1192 0.57
1.6
1276 0.67 1033 0.53
1.7
1137 0.63
1.8
1008 0.59
DSG060 HIGH STATIC BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6
2227 0.86 2050 0.73
0.7
2102 0.82 1932 0.69
0.8
2274 0.93 1999 0.79 1820 0.67
0.9
2304 1.03 2130 0.88 1859 0.76 1630 0.63
1.0
2162 0.98 2010 0.86 1694 0.72 1487 0.59
1.1
2325 1.15 2027 0.94 1820 0.79 1543 0.68 1267 0.55
1.2
2355 1.26 2247 1.11 1902 0.9 1721 0.77 1331 0.63
1.3
2247 1.22 2062 1.05 1768 0.87 1557 0.71
1.4
2151 1.19 1932 1.01 1579 0.82 1374 0.66
1.5
2004 1.14 1768 0.95 1339 0.74
1.6
1895 1.10 1637 0.91
1.7
1727 1.04
1331 0.8
1.8
1391 0.92
NOTE
Tables represent dry coil without filter, to compensate for filter add 0.08" to
measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5