background image

18

NATURALGAS

(Dia)

PROPANE (LP)

(Dia)

45,000

2

23,000

#43

#55

70,000

3

23,000

#43

#55

92,000

4

23,000

#43

#55

115,000

5

23,000

#43

#55

140,000

6

23,000

#43

#55

GAS ORIFICES

MAXIMUM 

INPUT

(BTUH)

NUMBER 

OF 

BURNERS

MAXIMUM 

BTUH/BURNER

Heat Exchanger and Burner Orifice Specifications

NOTE:

 Gas appliances located more than 2000 feet above 

sea level must be derated 4% per 1000 feet of total ele-

vation and that variance in gas heating value and specific 

gravity require change in manifold pressure to obtain rating, 

it is mandatory that the input be adjusted at the installation 

site. All installations should be made as outlined in the lat-

est edition of the National Fuel Gas Code ANSI Z223.1,sec-

tion “Procedures To Be Followed To Place An Appliance in 

Operation”. Refer also to the “User’s Information Manual” 

supplied with the unit for additional information on the gas 

furnace.

Gas Supply And Manifold Check

Gas supply pressure and manifold pressure with the burners 

operating must be as specified on the rating plate.

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accor-

dance to the type of fuel being consumed.

With Power And Gas Off:

1.  Connect a water manometer or adequate gauge to the 

inlet pressure tap of the gas valve.

 

Inlet gas pressure can also be measured by removing the 

cap from the dripleg and installing a predrilled cap with a 

hose fitting.

With Power And Gas On:

2.  Put unit into heating cycle and turn on all other gas con-

suming appliances.

NATURAL

Min.   5.0" W.C., Max. 10.0" W.C.

PROPANE

Min. 11.0" W.C., Max. 14.0" W.C.

INLET GAS PRESSURE

NOTE:

  Inlet Gas Pressure Must Not Exceed the Maximum 

Value Shown.
If operating pressures differ from above, make necessary 

pressure regulator adjustments, check piping size, etc., and/

or consult with local utility.

Manifold Pressure Check 

The gas valve has a tapped opening to facilitate measure-

ment of the manifold pressure. A “U” Tube manometer hav-

ing a scale range from 0 to 12 inches of water should be 

used for this measurement. The manifold pressure must be 

measured with the burners operating.

1.  With disconnect switch open, remove field connected 

thermostat wire from terminal R, W1 and W2 on TB1.  

Place jumper wire between R, W1 and W2 to engage 

high stage heat. (note on 045 kbtu/hr units W2 is not 

used, only jumper R to W1).

2.  See Figure in input rating section for gas valve adjust-

ment.

To adjust the pressure regulator, remove the adjustment 

screw or cover on the gas valve. Turn out (counterclock-

wise) to decrease pressure, turn in (clockwise) to increase 

pressure. Only small variations in gas flow should be made 

by means of the pressure regulator adjustment. In no case 

should the final manifold pressure vary more than plus or 

minus 0.3 inches water column from the specified nominal 

pressure. Any  major  changes  in  flow  should  be  made  by 

changing the size of the burner orifices.  The measured in

-

put rate to the furnace must not exceed the rating specified 

on the unit rating plate.
For natural gas, the high stage manifold pressure must be 

between 3.2 and 3.8 inches water column (3.5 nominal). 

Low stage manifold pressure must be between 1.7 to 2.3 

inches water column (2.0 nominal).

3.  To set low fire rate on 090, 115 and 140 kbtu/hr: Open 

disconnect switch, and remove jumper from R to W2.  To 

set low fire manifold pressure, repeat steps above.  Refer

 

to Figure in input rating section for location of high and 

low stage adjustment.

For propane gas, the manifold pressure must be between 

9.7 and 10.3 inches water column (10.0 nominal). Low stage 

manifold must be between 5.7 and 6.3 inches water column 

(6.0 nominal).

Gas Input (Natural Gas Only) Check 

It is the responsibility of the contractor to adjust the gas input 

to the unit.

To measure the gas input use a gas meter and proceed as 

follows:

1.  Turn off gas supply to all other appliances except the unit.
2.  With the unit operating, time the smallest dial on the me-

ter for one complete revolution. If this is a 2 cubic foot dial, 

divide the seconds by 2; if it is a 1 cubic foot dial, use the 

seconds as is. This gives the seconds per cubic foot of 

gas being delivered to the unit.

3.  INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC 

FOOT

Example: 

Natural gas with a heating value of 1000 BTU per 

cubic foot and 34 seconds per cubic foot as determined by 

Step 2, then: 

 

Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: 

BTU content of the gas should be obtained from the gas 

supplier. This measured input must not be greater than 

shown on the unit rating plate. 

Adjust input rate by varying the adjustment of the gas pres-

sure regulator on the gas valve. All adjustments must be 

made with furnace operating at high fire and at normal oper

-

Summary of Contents for DSG SERIES

Page 1: ...PONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN...

Page 2: ...MMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE WHAT TO DO IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR B...

Page 3: ...cted to the venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas...

Page 4: ...eller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me de ventilation afin de v rifier si la taille et l inclinaison par rapport l horizontale sont conformes aux exig...

Page 5: ...thereof c Original invoice or certified copy thereof showing trade and other discounts or reductions d Copy of the inspection report issued by carrier repre sentative at the time damage is reported t...

Page 6: ...nt is not recommended To avoid possible illness or death of the building occupants do NOT locate outside air intake device economizer man ual fresh air intake motorized fresh air intake too close to a...

Page 7: ...y obstruction The unit should be in stalled remote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake NOTE If the 48 minimum is used on the control panel sid...

Page 8: ...frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts...

Page 9: ...e main power supply wiring to the unit and low voltage wir ing to accessory controls must be done in accordance with these instructions the latest edition of the National Electrical Code ANSI NFPA 70...

Page 10: ...any accessory wiring to low voltage terminal block TB1 in the main control box LOW VOLTAGE BLOCK MAIN POWER LOW VOLTAGE ENTRANCE POWER THRU THE CURB Power and Low Voltage Block Connections NOTE The l...

Page 11: ...eed the rated input shown on the rating plate Overfiring of the unit could result in premature heat exchanger failure Piping IMPORTANT NOTE To avoid possible unsatisfactory op eration or equipment dam...

Page 12: ...ect switch for the unit PROPANE GAS INSTALLATIONS WARNING TO AVOID PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK INSTALL A GAS DETECTING WARNING DEVICE...

Page 13: ...0 w c and must be no greater than 13 0 w c measured at the unit gas valve Unit will not function satisfactorily if supply gas pressure is less than 11 0 w c or greater than 13 0 w c 6 All pipe connect...

Page 14: ...UNIT AND PADLOCK IN THE OFF POSITION BEFORE SERVICNG FANS WARNING This unit is equipped with an electronic ignition device to automatically light the main burners It also has a power vent blower to e...

Page 15: ...or mance Once it is established that supply voltage will be maintained within the utilization range under all system conditions check and calculate if an unbalanced condition exists between phases Cal...

Page 16: ...ilure will occur Check you belt drive for ad equate run in belt tension by measuring the force required to deflect the belt at the midpoint of the span length Belt tension force can be measured using...

Page 17: ...nifold pressure and is intended to prevent over fir ing only Do not attempt adjustment of the built in pressure regulator unless the supply pressure is at least 7 0 w c on natural gas or 13 0 w c on p...

Page 18: ...stage heat note on 045 kbtu hr units W2 is not used only jumper R to W1 2 See Figure in input rating section for gas valve adjust ment To adjust the pressure regulator remove the adjustment screw or c...

Page 19: ...FIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR CAUTION 6 Relight all other appliances turned off in step 1 Be sure all pilot burners...

Page 20: ...ot shut down the venter motor Unit Shutdown 1 Set the thermostat to lowest setting 2 Turn off the electrical power supply to the unit 3 Remove the heat exchanger door on the side of the unit by removi...

Page 21: ...Blue Medium Speed Red Low Speed EEM Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the motor terminal block White is for fan only and gas heat Yellow is for co...

Page 22: ...MAINTENANCE REFER TO THIS MANUAL FOR ADDITIONAL ASSISTANCE OR INFORMATION CONSULT A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR ITEMS INHE...

Page 23: ...f each heating season This examination is necessary for continued safe operation Par ticular attention should be given to deterioration from corro sion or other sources This examination is accomplishe...

Page 24: ...be caused by nearly invisible coating on the sensor Remove the sensor and careful ly clean with steel wool Check wiring Check wiring for opens shorts and miswiring IMPORTANT If you have to frequently...

Page 25: ...0 SPEED TAP EXTERNAL STATIC PRESSURE ESP in w c STANDARD CFM AMPS WATTS RPM 0 10 1280 1 54 360 755 0 20 1215 1 50 345 800 0 30 1145 1 46 335 830 0 40 1080 1 42 325 870 0 50 1005 1 37 310 895 0 10 1485...

Page 26: ...0 SPEED TAP EXTERNAL STATIC PRESSURE ESP in w c STANDARD CFM AMPS WATTS RPM 0 10 1570 2 09 490 905 0 20 1520 2 06 480 920 0 30 1445 1 95 460 945 0 40 1375 1 89 440 970 0 50 1295 1 81 425 995 0 10 1715...

Page 27: ...1545 3 72 435 955 0 60 1505 3 80 520 990 0 70 1430 3 93 530 1020 0 80 1370 4 08 535 1040 0 90 1300 4 12 570 1070 0 10 1945 4 46 600 920 0 20 1910 4 57 620 940 0 30 1850 4 66 635 965 0 40 1795 4 78 655...

Page 28: ...50 1560 3 60 475 920 0 60 1520 3 70 490 945 0 70 1470 3 80 500 970 0 80 1410 3 94 510 995 0 90 1345 3 98 530 1035 0 10 2005 4 30 575 880 0 20 1965 4 41 590 900 0 30 1895 4 52 610 930 0 40 1835 4 63 62...

Page 29: ...31 1055 0 19 0 6 1948 0 74 1744 0 61 1446 0 44 1206 0 32 910 0 19 0 8 1654 0 63 1409 0 48 1096 0 31 1 0 1337 0 50 987 0 28 DSG060 STANDARD BELT DRIVE DOWN SHOT CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP...

Page 30: ...52 0 42 1 2 1755 0 85 1605 0 70 1364 0 57 1133 0 46 1 3 1640 0 80 1459 0 66 1224 0 53 983 0 43 1 4 1525 0 76 1313 0 61 1083 0 49 1 5 1410 0 72 1192 0 57 1 6 1276 0 67 1033 0 53 1 7 1137 0 63 1 8 1008...

Page 31: ...5 0 4 2002 0 65 1708 0 49 1438 0 36 1167 0 22 0 6 1910 0 67 1612 0 50 1330 0 37 1030 0 23 0 8 1813 0 69 1571 0 54 1222 0 36 989 0 25 1 0 1478 0 56 1142 0 32 1 2 1107 0 41 ESP In H2O TURNS OPEN 0 1 2 3...

Page 32: ...3 1 3 1821 0 89 1621 0 73 1360 0 59 1091 0 47 1 4 1694 0 84 1458 0 68 1202 0 55 1 5 1567 0 80 1324 0 63 1042 0 51 1 6 1417 0 75 1148 0 59 1 7 1262 0 70 1 8 1120 0 66 DSG060 HIGH STATIC BELT DRIVE HORI...

Page 33: ...PRESSURE DROP SCFM 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 in WG 0 02 0 04 0 05 0 07 0 09 0 12 0 14 0 17 0 21 0 24 0 28 Airflow Pressure Drop of Downflow Economizer for 3 to 6 Ton Roofto...

Page 34: ...0 460 3 60 460 3 60 7 8 52 0 7 8 52 0 Indoor Fan Motor DSG048 4B 13 1 83 1 0 25 0 25 1 1 40 0 25 0 25 460 3 60 Standard Belt Drive 1 00 DSG048 3B 208 230 3 60 DSG048 7B 575 3 60 4 4 33 0 6 1 41 0 DSG0...

Page 35: ...6 DRAIN THRU CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES BOTTOM VIEW OF UNIT 8 3 16 5 7 8 5 19 7 16 27 3 8 47 1 2 4 1 2 7 1 2 SUPPLY RETURN RETURN SUPPLY 12 17 7 3 8 11 25 6 1 4 4 7 8 NOTE Refer...

Page 36: ...MOUNT T1 P2 REQUIRED SCREW P3 135 120 150 FUSE 3 AMP MAX F1 WH YL RD RD 11 8 12 9 7 10 4 2 5 6 3 1 FS RD BK SEE NOTE 8 GREEN JUMPER COOL DI L1 HEAT UNUSED L2 BL BK YL YL PU BR BL RD YL WH GR BL P1 EC...

Page 37: ...SFORMER 208 240 1 60 0140L02898 C HPS LPS HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL HIGH VOLTAGE LOW VOLTAGE FIELD WIRING LINE VOLTAGE LOW VOLTAGE BL RD Y1 YL W BL G R W NO ECONOMI...

Page 38: ...NIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the wiring diagram on the unit for the most up...

Page 39: ...NIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the wiring diagram on the unit for the most up...

Page 40: ...R C 24V TR LS NOTE 6 SEE ALS PS RS 2 1 4 5 W R G 3 6 1 2 3 FS IGN VM TB1 LPS HPS 1 5 EM Y2Y1 GND YL RD YL WH RD RD YL RD BK BK RD BL BK BK PU RD COMP BK PU CM BR PK 240 PK BL BL 208 OR LS RD RD WH GR...

Page 41: ...LOW WITH PINK STRIP GR GREEN WIRE CODE BL BLUE PU PURPLE WH WHITE BK B BLACK BR BROWN OR ORANGE YL YELLOW 6 L1 AND L2 ON ICC CONTROLS IS 24V INPUT 7 SPEED TAP TERMINATIONS SHOWN ON DIAGRAM ARE REPRESE...

Page 42: ...DRIVE GND YL 208 240 3 60 SEE NOTE 5 RD YL RD IIC C RD RD L2 C T2 L1 T1 BK PU YL OR NOTE 8 GREEN JUMPER ALS GR PS RS PLF YL YL NOTE 4 BL W R GAS VALVE BR PU PU PU BK BR R G Y1 W1 OR RD FS IGN VM BL R...

Page 43: ...E FILED WIRING LINE VOLTAGE LOW VOLTAGE BL RD Y1 YL W BL G R W NO ECONOMIZER G RD Y1 PK WH W R RD WH GR C R YL GR Y1 G WH WITH ECONOMIZER OPTION C GR THERMOSTAT FIELD WIRING BL C 2 STAGE COOLING TB1 G...

Page 44: ...UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the wiring diagram on the unit for the most u...

Page 45: ...C EM L2 L3 COMPRESSOR COMPONENT LEGEND COMP ALS TR TRANSFORMER L2 C CM T3 COMP T3 T2 FC L1 C T1 T1 C T2 208 240 3 60 0140L05406 A HPS LPS HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL...

Page 46: ...BK BK POWER SUPPLY 240 3 60 W H BL IIC FC RD RD L2 C T2 T3 L3 L1 T1 BK BK PU YL COMP BK PU CM BR VMR OR YL RD D NOTE 6 SEE YL YL PU RD BL D ALS GR PS RS PLF YL YL NOTE 4 2 1 4 5 YL BL W R GAS VALVE 3...

Page 47: ...SURE FLAME ROLLOUT FLAME SENSOR GAS VALVE GAS FLOW PLF NOTE 4 4 3 2 1 5 6 GV C T3 LOW SPEED T4 HIGH SPEED IGN NOTE 6 L1 F D1 FS TR L1 240 3 60 SUPPLY VOLTAGE CM CONDENSER MOTOR NOTE 6 FS IIC L2 VM 1 V...

Page 48: ...L 1 240 2 3 C BK OR RD OR BL GR SEE NOTE 3 FS IGN BK VM OR RD FC RD BR RD T2 T3 T1 C BC BK 208 L3 L2 L1 WH YL HPS LPS PK TB1 YL PK BL PK GR RD TO THERMOSTAT 3 1 2 F C OR OR SEE NOTE 4 BK BK BK GND T3...

Page 49: ...LUE PU PURPLE PK PINK WH WHITE BK BLACK RD RED BR BROWN OR ORANGE YL YELLOW VM 5 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER INSTALLER SERVICEMAN TR...

Page 50: ...E GND T3 RD L3 POWER SUPPLY YL BK 208 240 3 60 YL IIC T1 T2 BK PU YL BK RD C L1 L2 BL BL RD RD BK PU COMP CM BR BK RD RD LS WH GR BL PU RD RD WH BR YL RD BL RD YL YL GR YL PU YL PU PS 5 4 1 2 NOTE 2 P...

Page 51: ...LOWER CONTACTOR BC L2 L3 C CM T3 C FC 208 240 3 60 T2 T3 T2 T1 T1 L1 C SUPPLY VOLTAGE 3 VMR BC IIC VMR FS IGN NOTE 3 C RS GV 3 6 PLF 2 5 NOTE 2 1 EM LS H C D1 FS F 5 4 NOTE 3 ALS PS 10 3 6 8 12 11 9 I...

Page 52: ...OWER SUPPLY GR YL PK BL PK OR WH BK OR L3 L2 L1 LPS HPS OR RD BK BC C T3 T1 T2 PK RD BR BR RD FC RD OR VM BK IGN FS NOTE 3 SEE YL OR BK 460 575 TR 240 C 460 BL BL TR 24V BL VMR 3 1 2 WH RD EM OR BK RD...

Page 53: ...OR GAS VALVE IGNITOR EQUIPMENT GROUND FLAME SENSOR EVAPORATOR MOTOR FC FUSE F C GV FS GND IGN IIC EM COMPRESSOR COMPONENT LEGEND COMP ALS OPTI ONAL HIGH VOLTAGE HI GH VOLTAGE FIELD WIRING LOW VO LTAGE...

Page 54: ...ND T3 RD OR L3 YL BK GR YL IIC T1 T2 BK PU YL BK RD C L1 L2 BL BL RD OR BK BK PU COMP CM BR BK RD RD LS WH GR BL PU RD RD RD WH BR YL RD BL YL YL BL YL PU YL PU PS 5 4 1 2 NOTE 2 PLF 6 3 YL RS ALS GR...

Page 55: ...MER TR LOW VOLTAGE FACTORY WIRING LINE VOLTAGE LOW VOLTAGE FIELD WIRING HIGH VOLTAGE OPTIONAL HIGH VOLTAGE ALS COMP COMPONENT LEGEND COMPRESSOR EM IIC IGN GND FS GV C F FUSE FC EVAPORATOR MOTOR FLAME...

Page 56: ...56 WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS ARE LOCATED IN SUPPLEMENT IOD S1024 For complete information and installation instructions for models with DDC controls see manual DK DDC TGD 01...

Page 57: ...57 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 58: ...y service maintenance and proper unit operation Verify proper weatherproofing of all ductwork roof curbs and electrical connections Check that the flue screen is in place Check gas piping for leaks Ve...

Page 59: ...ondenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Circuit 1 Heating Supp...

Page 60: ...Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed...

Reviews: