APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE STANDARD SOWN SHOT
DSG036 STANDARD BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
1596 0.36 1368 0.28 1162 0.21
0.4
1468 0.37 1224 0.28 981 0.20
0.6
1610 0.51 1383 0.39 1124 0.28 856 0.19
0.8
1293 0.40 1021 0.29 776 0.20
1.0
948 0.29 614 0.17
DSG048 STANDARD BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
1891 0.56 1632 0.42 1391 0.30
0.4
1796 0.57 1533 0.43 1290 0.31 1055 0.19
0.6
1948 0.74 1744 0.61 1446 0.44 1206 0.32 910 0.19
0.8
1654 0.63 1409 0.48 1096 0.31
1.0
1337 0.50 987 0.28
DSG060 STANDARD BELT DRIVE DOWN SHOT
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
2210 0.91 2041 0.76 1869 0.63 1739 0.52 1565 0.40
0.4
2197 0.98 2021 0.82 1841 0.67 1660 0.54 1521 0.44 1339 0.32
0.6
2002 0.88 1822 0.72 1635 0.58 1445 0.44 1288 0.35
0.8
1799 0.77 1610 0.62 1425 0.48
1.0
1587 0.67 1384 0.51
NOTE
TURNS OPEN
ESP, In
H
2
O
4
5
0
1
2
3
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
Tables represent dry coil without filter, to compensate for filter add 0.08" to
measured E.S.P.
SCFM correction for wet coil = 4 %.