Circuit Functions
OVERHEATING CONTROL STATUS
OPERATION
The measurement of refrigerant flow to the evaporator is the
exclusive function of a TXV. It must measure this flow at precisely
the same rate at which the refrigerant is evaporated by the heat
charge.
The TXV does this by maintaining the coil with enough refrigerant
to maintain the correct superheat of the suction gas leaving the
evaporator coil.
The TXV regulates flow in response to charge superheat.
TXV Operation
If it is suspected that a TXV is not operating properly, checking
for overheating is the only way to be sure. Do this with precision
instrumentation to obtain meaningful results.
Operating overheat of 8°F to 12°F are considered normal. Here
are some “tips” to help in detecting and fixing performance
failures in a TXV:
• Check the bulb to make sure it is properly connected to
the suction line. If you can move the bulb manually, it is not
properly secured.
• The bulb must be perfectly insulated to protect it against the
effects of a draft.
• Check the equalizer line for restrictions (kinks) or signs of
frost. A frosted equalizer line indicates internal leakage and
will require valve replacement. Repair or replacement of
a bent equalizer will be necessary for the valve to operate
properly.
TXVs are designed to measure liquid refrigerant flow. If the
refrigerant at the valve inlet contains flash gas, the valve capacity
will be reduced. Make sure that the system is properly charged
and that there is some subcooling at the valve inlet before
discarding the TXV.
Dimensions (Mm)
Adjustable - ODF connections with 1/4” equalizer
Non-adjustable - Odf connections with 1/4” equalizer
Connections
Dimensions
A
B
C
D
3/8 ODF
41.9
41.9
9.6 (3/8)
8.6
1/2 ODF
41.9
41.9
12.8 (1/2)
12.2
5/8 ODF
54.6
54.6
16.0 (5/8)
19.0
7/8 ODF
54.6
54.6
22.3 (7/8)
19.0
1-1/8 ODF
61.0
61.0
28.7 (1-
1/8)
23.1
Summary of Contents for Clima-Flex CLIC Series
Page 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Page 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Page 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Page 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Page 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Page 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Page 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Page 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Page 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 118: ...iom clic cf eng www clima flex com...