iom-clic-cf-eng
www.clima-flex.com
8
!
DANGER
!
Improper rigging, lifting or moving of a unit can result in property damage, serious personal injury or death. Follow the rigging and
moving instructions carefully. Do not stand under the unit while it is being lifted or installed.
Maximum standby ambient temperature
130°F (54°C)
Maximum operating ambient temperature
113°F (45°C)
Minimum operating ambient temperature (standard control)
55°F(12°)
Outgoing chilled water temperature
40°F to 65°F (4°C to 18°C)
Outgoing chilled fluid temperatures (with antifreeze) - Note that in cases of high ambient tempera-
ture, the lowest outgoing water temperature settings may be outside the chiller’s operating enve-
lope; see the chiller’s operating envelope. Outgoing water temperature settings may be outside the
chiller’s operating envelope; refer to the Clima Flex Tools to make sure that the chiller is capable of
the required elevation.
15°F to 65°F (-9°C to
18°C)
Maximum evaporator inlet fluid temperature
81°F (27°C)
Maximum non-operating evaporator inlet fluid temperature
100°F (38°C)
NAMEPLATES
The unit nameplate is located on the outside of the unit power panel. Both the model number and serial number are located on the unit
nameplates; the serial number is unique to the unit.
These numbers should be used to identify the unit in case of service, parts or warranty questions. This nameplate also contains the
unit’s refrigerant charge and electrical ratings. The evaporator nameplate is under the insulation and contains the serial number. The
compressor nameplate is located on each compressor and provides pertinent electrical information.
!
WARNING
!
Installation should be performed by qualified personnel who are familiar with local codes and regulations.
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report shipping damage and file a claim with
the carrier. Check the unit nameplate before unloading, making sure it matches the available power supply.
Clima Flex is not responsible for physical damage that occurs after the unit leaves the factory.
Take care to avoid rough handling of the unit. Do not push or pull the unit from other than the base while seated on properly sized dollies.
To lift the unit, 2-1/2 (64 mm) diameter lifting eyes are provided at the base of the unit. Arrange the spreader bars and cables to prevent
damage to the condenser coils or cabinet (see Figure 1).
!
CAUTION
!
All lifting locations must be used to avoid damage to the unit.
Installation and Application Information
INSPECTION
HANDLING
OPERATING AND STANDBY LIMITS
Table 1.
Table unit CLIC
Summary of Contents for Clima-Flex CLIC Series
Page 39: ...iom clic cf eng www clima flex com 39 Electrical Data...
Page 41: ...iom clic cf eng www clima flex com 41 Electrical Data...
Page 43: ...iom clic cf eng www clima flex com 43 Electrical Data...
Page 45: ...iom clic cf eng www clima flex com 45 Electrical Data...
Page 46: ...iom clic cf eng www clima flex com 46 Electrical Data...
Page 48: ...iom clic cf eng www clima flex com 48 Electrical Data...
Page 53: ...iom clic cf eng www clima flex com 53 R454B Electrical Data Figure 38 RS485 communication...
Page 77: ...iom clic cf eng www clima flex com 77 Clic R454b Unit This unit use the R454B Refrigerant...
Page 117: ...iom clic cf eng www clima flex com 117 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 118: ...iom clic cf eng www clima flex com...