13 Configuration
Installer and user reference guide
30
BRK+S7
Wired remote controller
4P513689-1D – 2019.05
Parameter
Description
Possible values
Default value
Reset ON/OFF
"Default Reset Setting"
on/off
state
"ON", "OFF", "--"
"OFF"
Reset Mode
"Default Reset Setting"
operation
mode
Auto, Cooling, Heating, Fan only,
--
"--"
Reset Cool SP
"Default Reset Setting"
cooling
setpoint
See indoor unit's setpoint range
and setpoint range limitation, "--"
"22°C"
Reset Heat SP
"Default Reset Setting"
heating
setpoint
See indoor unit's setpoint range
and setpoint range limitation, "--"
"22°C"
INFORMATION
When the value for a parameter is "- -", this means that
when the timers expires, nothing changes for that
parameter and the current active value is kept.
Window contact logic
Window contact B1
Key card contact B2
Time
Action
Contact closed (window closed)
Contact closed (key card IN)
—
▪ Normal indoor unit operation.
▪ The unit returns to the previous
state
before
opening
the
contact.
Contact open (window open)
Contact closed (key card IN)
—
Unit operation is forced off:
▪ No delay and reset timer
functionality.
▪ No Setback functionality.
▪ Not possible to turn on/off the
unit with the controller's ON/OFF
button.
Key card contact logic
Window contact B1
Key card contact B2
Time
Action
Contact closed (window closed)
Contact closed (key card IN)
▪ —
▪ Delay timer<Time<Reset timer
▪ Time>Reset timer
▪ The unit operates normally.
▪ If the reset timer has not
expired, the unit returns to the
previous state before opening
the contact.
▪ If the reset timer has expired,
the unit returns to the
"Default
Reset Setting"
(see
).
Contact closed (window closed)
Contact open (key card OUT)
Time<Delay timer
Normal indoor unit operation.