13 Configuration
Installer and user reference guide
29
BRK+S7
Wired remote controller
4P513689-1D – 2019.05
Result:
You assigned an AirNet address to the outdoor unit.
To remove an address
1
Navigate to the address that you want to remove.
2
Change
to
.
3
Confirm your selection.
Result:
The address gets removed.
External input interlock
About external input interlock
External input interlock allows for the integration of external contacts
in the system's control logic. By adding a key card contact and/or a
window contact to the control setup, it is possible to have the system
respond to the insertion/removal of a key card in/from a card reader,
and/or the opening/closing of windows.
INFORMATION
To use this function, it is required that digital input adapter
BRP7A5* is part of the system.
▪ Make sure that the digital input adapter and its optional
contacts (window contact B1 and key card contact B2)
are correctly installed. Confirm that the voltage free
contact of the digital input adapter is in the correct
position. For instructions on how to install the digital
input adapter, see the installation manual of the digital
input adapter.
▪ When the digital input adapter does not function
properly, external input interlock is not available in the
menu.
▪ When the digital input adapter is part of the system, the
system does not allow for the connection of a slave
controller.
▪ When the digital input adapter is part of the system, it is
not possible to use the Schedule function.
▪ When the digital input adapter is part of the system, as
well as a centralised controller, the external input
interlock function is controlled by the centralised
controller, and not by the adapter.
To make external input interlock settings
Prerequisite:
You are in the installer menu.
1
Navigate to the external input interlock menu.
2
Use
and
to navigate through the menu.
3
Press
to select a parameter.
4
With a parameter selected, use
and
to change that
parameter's value.
5
With a parameter selected, press
to confirm the value for
that parameter.
6
When you are done making settings, confirm all settings by
selecting
and pressing
.
Result:
The system will restart and implement any changes made.
INFORMATION
For an overview of settable parameters and what they
mean, see
"External input interlock settings overview" on
.
External input interlock settings overview
Parameter
Description
Possible values
Default value
B2
Delay Timer
Timer that starts as soon as the
key card is removed. The unit
continues normal operation until
the timer expires.
0-10 minutes
"1 min"
B2
Reset Timer
Timer that starts as soon as the
Delay Timer expires. When this
timer expires, the previous state
(i.e. regular setpoint) changes to
the
"Default Reset Setting"
state.
0-20 hours
"20 hours"