Indoor Unit Installation

5.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of Hose Front End]

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 16 mm. Be sure to 
thermally insulate the indoor section of the extension hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with 
embedded piping work, use any commercially 
available drain socket (nominal diameter 13mm) 
as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

ø18

ø16

ø16

The drain hose provided 
to indoor unit.

Indoor unit 
drain hose

ø16

Extension drain hose

Heat insulation tube
(Field supply)

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe 
(nominal diameter 13mm)

The drain hose provided 
to indoor unit.

ø18

A

A

(Cut exactly at 
right angles.)

Remove burrs

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

(Ridgid-type)

1.5-2.0mm

(Imperial-type)

Conventional flare tool

3PEN341265-5Q.book  Page 10  Friday, March 17, 2017  10:56 AM

Summary of Contents for ATXB25C

Page 1: ...5C2V1B FTXB35C2V1B ATXB25C2V1B ATXB35C2V1B 3PEN341265 5Q book Page 1 Friday March 17 2017 10 56 AM Questo manuale d istruzione fornito da trovaprezzi it Scopri tutte le offerte per Daikin ATXB25C o ce...

Page 2: ...orado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer po...

Page 3: ...ric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor units Firmly clamp the interconnecting wires so their terminals receive no external stresse...

Page 4: ...e room if any and find the site where remote control signals are properly received by the indoor unit within 7 metres CAUTION Do not install the air conditioner in a place where there is danger of exp...

Page 5: ...s of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing...

Page 6: ...weight of the indoor unit Mounting plate Screws Field supply M4 25L M4 16L 75mm or more from ceiling Front panel 50mm or more from walls on both sides Air filters Service lid Opening service lid Servi...

Page 7: ...nded mounting plate retention spots and Dimensions Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The...

Page 8: ...insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 4...

Page 9: ...right to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it...

Page 10: ...s stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire 2 Do not use locally purchased electrical parts inside the product Do not branch the po...

Page 11: ...HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHAR...

Page 12: ...l oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts...

Page 13: ...urface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as...

Page 14: ...he circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Trial operation from rem...

Page 15: ...3PEN341265 5Q book Page 1 Friday March 17 2017 10 56 AM...

Page 16: ...3P341265 5Q 2017 02 Copyright 2014 Daikin 3PEN341265 5Q book Page 2 Friday March 17 2017 10 56 AM...

Reviews: