Refrigerant Piping Work

2.

Refrigerant piping.

 CAUTION

1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. 

2-1. Caution on piping handling.

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

2-2. Selection of copper and heat insulation materials.

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045 kcal/(mh•°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.

[Apply oil]

Piping union

Flare nut

Spanner

[Tighten]

3/8 inch

1/4 inch

Torque wrench

Flare nut tightening torque

Gas side

32.7-39.9N • m

(330-407kgf • cm)

14.2-17.2N • m

(144-175kgf • cm)

Liquid side

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt 
or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Inter-unit wiring

Liquid pipe

Drain hose

Finishing tape

Gas pipe 

insulation

Liquid pipe 

insulation

3PEN341265-5Q.book  Page 11  Friday, March 17, 2017  10:56 AM

Summary of Contents for ATXB25C

Page 1: ...5C2V1B FTXB35C2V1B ATXB25C2V1B ATXB35C2V1B 3PEN341265 5Q book Page 1 Friday March 17 2017 10 56 AM Questo manuale d istruzione fornito da trovaprezzi it Scopri tutte le offerte per Daikin ATXB25C o ce...

Page 2: ...orado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer po...

Page 3: ...ric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor units Firmly clamp the interconnecting wires so their terminals receive no external stresse...

Page 4: ...e room if any and find the site where remote control signals are properly received by the indoor unit within 7 metres CAUTION Do not install the air conditioner in a place where there is danger of exp...

Page 5: ...s of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing...

Page 6: ...weight of the indoor unit Mounting plate Screws Field supply M4 25L M4 16L 75mm or more from ceiling Front panel 50mm or more from walls on both sides Air filters Service lid Opening service lid Servi...

Page 7: ...nded mounting plate retention spots and Dimensions Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liquid pipe end Gas pipe end The...

Page 8: ...insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 4...

Page 9: ...right to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it...

Page 10: ...s stranded wires extension cords or starburst connections as they may cause overheating electrical shock or fire 2 Do not use locally purchased electrical parts inside the product Do not branch the po...

Page 11: ...HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHAR...

Page 12: ...l oil on flared part 2 Prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts...

Page 13: ...urface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as...

Page 14: ...he circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Trial operation from rem...

Page 15: ...3PEN341265 5Q book Page 1 Friday March 17 2017 10 56 AM...

Page 16: ...3P341265 5Q 2017 02 Copyright 2014 Daikin 3PEN341265 5Q book Page 2 Friday March 17 2017 10 56 AM...

Reviews: