Outdoor Unit - RK(X)S50G2V1B, ARXS50G2V1B
Removal Procedure
272
7
Unfasten the hooks and
remove the right side
panel.
When reassembling, insert
the 2 hooks of the lower part
and the 1 hook of the upper
back.
8
Disconnect the
connectors of the front
side.
[S20]: electronic
expansion valve
coil
[S40]: overload
protector
[S80]: four way valve
coil
[S90]: thermistors
9
Disconnect the relay
connector for the
compressor.
Step
Procedure
Points
(R5272)
Hook
(R5273)
Hooks
(R5275)
[S40] [S20]
[S90]
[S80]