Troubleshooting
SiENBE04-808_A
117
Service Diagnosis
4.12 Input Overcurrent Detection
Remote Control
Display
E8
Method of
Malfunction
Detection
An input overcurrent is detected by checking the input current value with the compressor
running.
Malfunction
Decision
Conditions
The following current with the compressor running continues for 2.5 seconds.
Cooling / Heating: Above 9.25 ~ 20 A (Refer to “Input current control” on page 51 for detail.)
Supposed
Causes
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.07
Refer to P.149
Check No.08
Refer to P.149
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
∗
An input overcurrent may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input overcurrent,
take the following procedure.
(R11709)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
Check with the inverter checker (
∗
).
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB.
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
Any LED off?
Input current
flowing above its stop level?
∗
Inverter checker
Part No.: 1225477
SiENBE04-808_A.pdf 129
21/02/2011 13:20:02