2 About the box

Installation manual

5

08S18+23DA + 08S18+23DJ
Daikin Altherma 3 R F
4P584429-1 – 2019.06

2

About the box

2.1

Indoor unit

2.1.1

To remove the accessories from the
indoor unit

a

b

g

h

i

c

d

e

f

a

Shut-off valves for water circuit

b

Overpressure bypass valve

c

General safety precautions

d

Addendum book for optional equipment

e

Indoor unit installation manual

f

Operation manual

g

Sealing rings for shut-off valves (space heating water
circuit)

h

Sealing rings for field-supplied shut-off valves (domestic
hot water circuit)

i

Sealing tape for low voltage wiring intake

2.1.2

To handle the indoor unit

Use the handles at the back and at the bottom to carry the unit.

b

a

a

b

a

Handles at the back of the unit

b

Handles at the bottom of the unit. Carefully tilt the unit to
the back so that the handles become visible.

3

Preparation

3.1

Preparing the installation site

NOTICE

This unit is designed for operation on 2 temperature zones:

▪ underfloor  heating  in  the 

main  zone

,  this  is  the  zone

with the 

lowest water temperature

,

▪ radiators  in  the 

additional  zone

,  this  is  the  zone  with

the 

highest water temperature

.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

DO  NOT  reuse  refrigerant  piping  that  has  been  used  with
any  other  refrigerant.  Replace  the  refrigerant  pipes  or
clean thoroughly.

3.1.1

Installation site requirements of the
indoor unit

▪ The indoor unit is designed for indoor installation only and for the

following ambient temperatures:

▪ Space heating operation: 5~30°C

▪ Domestic hot water production: 5~35°C

▪ Mind the following spacing installation guidelines:

≥300

≥500

(mm)

≥600

INFORMATION

If  you  have  limited  installation  space,  do  the  following
before  installing  the  unit  in  its  final  position: 

"4.2.2  To

connect  the  drain  hose  to  the  drain"  on  page  10

.  It

requires to remove one or both side panels.

NOTICE

When the temperature in multiple rooms is controlled by 1
thermostat,  do  NOT  place  a  thermostatic  valve  on  the
emitter in the room where the thermostat is installed.

Special requirements for R32

WARNING

▪ Do NOT pierce or burn.

▪ Do  NOT  use  means  to  accelerate  the  defrosting

process  or  to  clean  the  equipment,  other  than  those
recommended by the manufacturer.

▪ Be  aware  that  R32  refrigerant  does  NOT  contain  an

odour.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

NOTICE

▪ Do NOT re-use joints which have been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

Summary of Contents for Altherma EHVZ08S23DA6V

Page 1: ...Altherma 3 R F English Installation manual Daikin Altherma 3 R F EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G EHVZ04S18DJ6V G EHVZ08S18DJ6V G EHVZ08S23DJ6V G EHVZ08...

Page 2: ...du s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im upu...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...nd date 18 5 2 3 Configuration wizard System 18 5 2 4 Configuration wizard Backup heater 19 5 2 5 Configuration wizard Main zone 19 5 2 6 Configuration wizard Additional zone 20 5 2 7 Detailed screen...

Page 5: ...e refrigerant pipes or clean thoroughly 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Spac...

Page 6: ...ion Installation manual 6 EHVZ04 08S18 23DA EHVZ04 08S18 23DJ Daikin Altherma 3 R F 4P584429 1 2019 06 NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to...

Page 7: ...Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings...

Page 8: ...y 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 f 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free...

Page 9: ...ower the switch box on the indoor unit on page 9 4 2 2 To connect the drain hose to the drain on page 10 When you need access to the high voltage switch box 4 1 2 To open the switch box cover of the i...

Page 10: ...he drain pan The drain pan is connected to a drain hose inside the unit You must connect the drain hose to an appropriate drain according to the applicable legislation You can route the drain hose thr...

Page 11: ...ter in c Domestic hot water out d Domestic cold water in cold water supply e Space heating main zone water out f Space heating main zone water in NOTICE It is recommended to install shut off valves to...

Page 12: ...unit 1 To open the indoor unit see 4 1 1 To open the indoor unit on page 8 and 4 1 2 To open the switch box cover of the indoor unit on page 9 2 The wiring enters the unit from the top b c a d a b c F...

Page 13: ...pply WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed...

Page 14: ...actor in the lower switch box K5M Safety contactor in the lower switch box Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the back...

Page 15: ...ector backup heater Do NOT change 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space heating ON OFF output 1 Connect the space heating ON OFF output cable to the app...

Page 16: ...rmostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFOR...

Page 17: ...nstaller settings on page 23 5 1 1 To access the most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Ente...

Page 18: ...ng Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of do...

Page 19: ...y 1 2 a 2 Relay 1 Relay 2 a 3 Relay 1 Relay 2 Emergency Relay 1 2 a a Not available for 3V models INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you chang...

Page 20: ...aving water temperatures either preset or custom In Weather dependent LWT setpoint mode the scheduled actions consist of desired shift actions either preset or custom Code Description 2 1 N A 0 No 1 Y...

Page 21: ...reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has...

Page 22: ...rmostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OF...

Page 23: ...step 2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum run...

Page 24: ...e of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pi...

Page 25: ...e 17 2 Go to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when done 30 min To stop the te...

Page 26: ...setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to sta...

Page 27: ...mixed zone c1 Domestic hot water cold water IN c2 Domestic hot water hot water OUT d1 Gas refrigerant IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger...

Page 28: ...ostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in swit...

Page 29: ...e 5 Ext thermistor 5 External thermistor SWB Switch box 6 Field supplied options 6 Field supplied options English Translation 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection vo...

Page 30: ...signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H onl...

Page 31: ...0 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between...

Page 32: ...4P584429 1 2019 06 Copyright 2017 Daikin 4P584429 1 0000000U...

Reviews: