background image

5 Configuration

Installation manual

19

08S18+23DA + 08S18+23DJ
Daikin Altherma 3 R F
4P584429-1 – 2019.06

CAUTION

If  there  are  2  zones,  it  is  important  that  the  zone  with  the
lowest  water  temperature  is  configured  as  the  main  zone,
and  the  zone  with  the  highest  water  temperature  is
configured  as  the  additional  zone.  Not  configuring  the
system  in  this  way  could  cause  damage  to  the  heat
emitters.

CAUTION

If  there  are  2  zones  and  the  emitter  types  are  wrongly
configured, water of high temperature can be sent towards
a  low  temperature  emitter  (underfloor  heating).  To  avoid
this:

▪ Install an aquastat/thermostatic valve to avoid too high

temperatures towards a low temperature emitter.

▪ Make sure you set the emitter types for the main zone

[2.7]  and  for  the  additional  zone  [3.7]  correctly  in
accordance with the connected emitter.

NOTICE

An  overpressure  bypass  valve  can  be  integrated  in  the
system.  Keep  in  mind  that  this  valve  might  not  be  shown
on the illustrations.

5.2.4

Configuration wizard: Backup heater

The  backup  heater  is  adapted  to  be  connected  to  most  common
European  electricity  grids.  If  the  backup  heater  is  available,  the
voltage,  configuration  and  capacity  must  be  set  on  the  user
interface.

The  capacities  for  the  different  steps  of  the  backup  heater  must  be
set  for  the  energy  metering  and/or  power  consumption  control
feature  to  work  properly.  When  measuring  the  resistance  value  of
each heater, you can set the exact heater capacity and this will lead
to more accurate energy data.

Voltage

▪ For a 

3V

 model, this is fixed to 

230V, 1ph

.

▪ For a 

6V

 model, this can be set to:

230V, 1ph

230V, 3ph

▪ For a 

9W

 model, this is fixed to 

400V, 3ph

.

#

Code

Description

[9.3.2]

[5‑0D]

▪ 0: 

230V, 1ph

▪ 1: 

230V, 3ph

▪ 2: 

400V, 3ph

Configuration

The  backup  heater  can  be  configured  in  different  ways.  It  can  be
chosen to have a 1-step only backup heater or a backup heater with
2 steps. If 2 steps, the capacity of the second step depends on this
setting.  It  can  also  be  chosen  to  have  a  higher  capacity  of  the
second step in emergency.

#

Code

Description

[9.3.3]

[4‑0A]

▪ 0: Relay 1

▪ 1: Relay 1 / Relay 1+2

(a)

▪ 2: Relay 1 / Relay 2

(a)

▪ 3: Relay 1 / Relay 2 

Emergency

 Relay

1+2

(a)

(a)

Not available for 

3V

 models.

INFORMATION

Settings  [9.3.3]  and  [9.3.5]  are  linked.  Changing  one
setting influences the other. If you change one, check if the
other is still as expected.

INFORMATION

During normal operation, the capacity of the second step of
the  backup  heater  at  nominal  voltage  is  equal  to
[6‑03]+[6‑04].

INFORMATION

If  [4‑0A]=3  and  emergency  mode  is  active,  the  power
usage  of  the  backup  heater  is  maximal  and  equal  to
2×[6‑03]+[6‑04].

INFORMATION

Only for systems with integrated domestic hot water tank: If
the  storage  temperature  set  point  is  higher  than  50°C,
Daikin  recommends  NOT  to  disable  the  backup  heater
second  step  because  it  will  have  a  big  impact  on  the
required time for the unit to heat up the domestic hot water
tank.

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

5.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Depending on the system water volume and the heater emitter type
of the main zone, the heat up of the main zone can take longer. This
setting can compensate for a slow or a quick heating system during
the heat up cycle. The target delta T for the main zone will depend
on this setting. Target delta T control is only possible in case only 1
zone  is  active.  Pump  control  will  be  different  when  both  zones  are
active.

In  room  thermostat  control,  this  setting  will  influence  the  maximum
modulation of the desired leaving water temperature.

Therefore it is important to set this correctly and in accordance with
your system layout.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 65°C

Fixed 10°C

Summary of Contents for Altherma EHVZ08S23DA6V

Page 1: ...Altherma 3 R F English Installation manual Daikin Altherma 3 R F EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G EHVZ04S18DJ6V G EHVZ08S18DJ6V G EHVZ08S23DJ6V G EHVZ08...

Page 2: ...du s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im upu...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...nd date 18 5 2 3 Configuration wizard System 18 5 2 4 Configuration wizard Backup heater 19 5 2 5 Configuration wizard Main zone 19 5 2 6 Configuration wizard Additional zone 20 5 2 7 Detailed screen...

Page 5: ...e refrigerant pipes or clean thoroughly 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Spac...

Page 6: ...ion Installation manual 6 EHVZ04 08S18 23DA EHVZ04 08S18 23DJ Daikin Altherma 3 R F 4P584429 1 2019 06 NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to...

Page 7: ...Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings...

Page 8: ...y 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 f 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free...

Page 9: ...ower the switch box on the indoor unit on page 9 4 2 2 To connect the drain hose to the drain on page 10 When you need access to the high voltage switch box 4 1 2 To open the switch box cover of the i...

Page 10: ...he drain pan The drain pan is connected to a drain hose inside the unit You must connect the drain hose to an appropriate drain according to the applicable legislation You can route the drain hose thr...

Page 11: ...ter in c Domestic hot water out d Domestic cold water in cold water supply e Space heating main zone water out f Space heating main zone water in NOTICE It is recommended to install shut off valves to...

Page 12: ...unit 1 To open the indoor unit see 4 1 1 To open the indoor unit on page 8 and 4 1 2 To open the switch box cover of the indoor unit on page 9 2 The wiring enters the unit from the top b c a d a b c F...

Page 13: ...pply WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed...

Page 14: ...actor in the lower switch box K5M Safety contactor in the lower switch box Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the back...

Page 15: ...ector backup heater Do NOT change 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space heating ON OFF output 1 Connect the space heating ON OFF output cable to the app...

Page 16: ...rmostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFOR...

Page 17: ...nstaller settings on page 23 5 1 1 To access the most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Ente...

Page 18: ...ng Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of do...

Page 19: ...y 1 2 a 2 Relay 1 Relay 2 a 3 Relay 1 Relay 2 Emergency Relay 1 2 a a Not available for 3V models INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you chang...

Page 20: ...aving water temperatures either preset or custom In Weather dependent LWT setpoint mode the scheduled actions consist of desired shift actions either preset or custom Code Description 2 1 N A 0 No 1 Y...

Page 21: ...reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has...

Page 22: ...rmostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OF...

Page 23: ...step 2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum run...

Page 24: ...e of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pi...

Page 25: ...e 17 2 Go to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when done 30 min To stop the te...

Page 26: ...setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to sta...

Page 27: ...mixed zone c1 Domestic hot water cold water IN c2 Domestic hot water hot water OUT d1 Gas refrigerant IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger...

Page 28: ...ostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in swit...

Page 29: ...e 5 Ext thermistor 5 External thermistor SWB Switch box 6 Field supplied options 6 Field supplied options English Translation 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection vo...

Page 30: ...signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H onl...

Page 31: ...0 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between...

Page 32: ...4P584429 1 2019 06 Copyright 2017 Daikin 4P584429 1 0000000U...

Reviews: