background image

4 Installation

Installation manual

13

08S18+23DA + 08S18+23DJ
Daikin Altherma 3 R F
4P584429-1 – 2019.06

Without low voltage cables

With low voltage cables

4.5.3

To connect the main power supply

1

Connect the main power supply.

In case of normal kWh rate power supply

X1M

X2M

X5M

A5P

X11YB

X1A

1 2 3
1 2 3

a

X11Y

X11YA

1 2 3

Legend: see illustration below.

In case of preferential kWh rate power supply

Connect X11Y to X11YB.

X1M

X2M

X5M

A5P

X11Y

X11YB

X1A

1 2 3
1

N L

N L

2 3

S1S

a

b

c

X11YA

5

1 2 3

6

9 10

a

Interconnection cable (=main power supply)

b

Normal kWh rate power supply

c

Preferential power supply contact

2

Fix the cables with cable ties to the cable tie mountings.

INFORMATION

In  case  of  preferential  kWh  rate  power  supply,  connect
X11Y  to  X11YB.  The  necessity  of  separate  normal  kWh
rate  power  supply  to  indoor  unit  (b)  X2M/5+6  depends  on
the type of preferential kWh rate power supply.

Separate connection to the indoor unit is required:

▪ if  preferential  kWh  rate  power  supply  is  interrupted

when active, OR

▪ if no power consumption of the indoor unit is allowed at

the preferential kWh rate power supply when active.

INFORMATION

The  preferential  kWh  rate  power  supply  contact  is
connected to the same terminals (X5M/9+10) as the safety
thermostat for the additional zone. It is only possible for the
system  to  have  EITHER  preferential  kWh  rate  power
supply OR a safety thermostat for the additional zone.

4.5.4

To connect the backup heater power
supply

WARNING

The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.

CAUTION

To  guarantee  the  unit  is  completely  earthed,  always
connect  the  backup  heater  power  supply  and  the  earth
cable.

The backup heater capacity can vary, depending on the indoor unit
model.  Make  sure  that  the  power  supply  is  in  accordance  with  the
backup heater capacity, as listed in the table below.

Backup

heater type

Backup

heater

capacity

Power

supply

Maximum

running

current

Z

max

*6V

2 kW

1N~ 230 V

(c)

9 A

4 kW

1N~ 230 V

(c)

17 A

(a)(b)

0.22 Ω

6 kW

1N~ 230 V

(c)

26 A

(a)(b)

0.22 Ω

2 kW

3~ 230 V

(d)

5 A

4 kW

3~ 230 V

(d)

10 A

6 kW

3~ 230 V

(d)

15 A

*9W

3 kW

3N~ 400 V

4 A

6 kW

3N~ 400 V

9 A

9 kW

3N~ 400 V

13 A

(a)

Equipment complying with EN/IEC 61000-3-12 (European/
International Technical Standard setting the limits for
harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and
≤75 A per phase.).

(b)

This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems for equipment with rated
current ≤75 A) provided that the system impedance Z

sys

 is

less than or equal to Z

max

 at the interface point between the

user's supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a system impedance Z

sys

 less than or equal to

Z

max

.

(c)

(6V)

(d)

(6T1)

Connect the backup heater power supply as follows:

Summary of Contents for Altherma EHVZ08S23DA6V

Page 1: ...Altherma 3 R F English Installation manual Daikin Altherma 3 R F EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ08S18DA9W G EHVZ08S23DA9W G EHVZ04S18DJ6V G EHVZ08S18DJ6V G EHVZ08S23DJ6V G EHVZ08...

Page 2: ...du s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im upu...

Page 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Page 4: ...nd date 18 5 2 3 Configuration wizard System 18 5 2 4 Configuration wizard Backup heater 19 5 2 5 Configuration wizard Main zone 19 5 2 6 Configuration wizard Additional zone 20 5 2 7 Detailed screen...

Page 5: ...e refrigerant pipes or clean thoroughly 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Spac...

Page 6: ...ion Installation manual 6 EHVZ04 08S18 23DA EHVZ04 08S18 23DJ Daikin Altherma 3 R F 4P584429 1 2019 06 NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to...

Page 7: ...Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings...

Page 8: ...y 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 f 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free...

Page 9: ...ower the switch box on the indoor unit on page 9 4 2 2 To connect the drain hose to the drain on page 10 When you need access to the high voltage switch box 4 1 2 To open the switch box cover of the i...

Page 10: ...he drain pan The drain pan is connected to a drain hose inside the unit You must connect the drain hose to an appropriate drain according to the applicable legislation You can route the drain hose thr...

Page 11: ...ter in c Domestic hot water out d Domestic cold water in cold water supply e Space heating main zone water out f Space heating main zone water in NOTICE It is recommended to install shut off valves to...

Page 12: ...unit 1 To open the indoor unit see 4 1 1 To open the indoor unit on page 8 and 4 1 2 To open the switch box cover of the indoor unit on page 9 2 The wiring enters the unit from the top b c a d a b c F...

Page 13: ...pply WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION To guarantee the unit is completely earthed...

Page 14: ...actor in the lower switch box K5M Safety contactor in the lower switch box Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the back...

Page 15: ...ector backup heater Do NOT change 2 Fix the cable with cable ties to the cable tie mountings 4 5 9 To connect the space heating ON OFF output 1 Connect the space heating ON OFF output cable to the app...

Page 16: ...rmostat is automatically resettable The safety thermostat has a maximum temperature variation rate of 2 C min There is a minimum distance of 2 m between the safety thermostat and the 3 way valve INFOR...

Page 17: ...nstaller settings on page 23 5 1 1 To access the most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Ente...

Page 18: ...ng Menu structure setting 9 2 1 replaces the following 3 overview settings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of do...

Page 19: ...y 1 2 a 2 Relay 1 Relay 2 a 3 Relay 1 Relay 2 Emergency Relay 1 2 a a Not available for 3V models INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you chang...

Page 20: ...aving water temperatures either preset or custom In Weather dependent LWT setpoint mode the scheduled actions consist of desired shift actions either preset or custom Code Description 2 1 N A 0 No 1 Y...

Page 21: ...reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a stop to tank heating even if the setpoint has...

Page 22: ...rmostat can only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OF...

Page 23: ...step 2 Capacity step 1 Equilibrium Equilibrium temperature Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum run...

Page 24: ...e of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pi...

Page 25: ...e 17 2 Go to A 1 Commissioning Operation test run 3 Select a test from the list Example Heating 4 Select OK to confirm Result The test run starts It stops automatically when done 30 min To stop the te...

Page 26: ...setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to sta...

Page 27: ...mixed zone c1 Domestic hot water cold water IN c2 Domestic hot water hot water OUT d1 Gas refrigerant IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger...

Page 28: ...ostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in swit...

Page 29: ...e 5 Ext thermistor 5 External thermistor SWB Switch box 6 Field supplied options 6 Field supplied options English Translation 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection vo...

Page 30: ...signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H onl...

Page 31: ...0 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between...

Page 32: ...4P584429 1 2019 06 Copyright 2017 Daikin 4P584429 1 0000000U...

Reviews: