4 Installation
Installation manual
14
08S18+23DA + 08S18+23DJ
Daikin Altherma 3 R F
4P584429-1 – 2019.06
X6M
F1B
Q1DI
a
b
a
Factory-mounted cable connected to the backup heater
contactor inside the switch box (K5M for *6V and *9W
models)
b
Field wiring (see table below)
Model (power
supply)
Connections to backup heater power
supply
*6V (6V: 1N~ 230 V)
1N~, 50 Hz
230 V AC
SWB
4
3
6
5
2
1
K5M
14
13
Q1DI
1
2
3
4
5
6
7
8
F1B
I
I
I
I
N
L
X6M
BRN
GRY
BLU1
BLU2
*6V (6T1: 3~ 230 V)
SWB
3~, 50 Hz
230 V AC
4
3
6
5
2
1
K5M
14
13
1
2
3
4
5
6
7
8
F1B
I
I
I
I
Q1DI
L1 L2 L3
X6M
BRN
GRY
BLU1
BLU2
Model (power
supply)
Connections to backup heater power
supply
*9W (3N~ 400 V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1 L2 L3 N
1
2
3
4
5
6
7
8
F1B
I
I
I
I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B
Overcurrent fuse (field supply). Recommended fuse for *6V
and *9W models: 4‑pole; 20 A; curve 400 V; tripping class
C.
K1M
Contactor (in the lower switch box)
K5M
Safety contactor (in the lower switch box)
Q1DI
Earth leakage circuit breaker (field supply)
SWB
Switch box
X6M
Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply
cable.
4.5.5
To connect the shut-off valve
INFORMATION
Shut-off valve usage example.
In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation. For more information, see the installer reference
guide.
1
Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
X1M
X2M
X1M
X2M
NO
M2S
NC
M2S
21 28
21 29
2
Fix the cable with cable ties to the cable tie mountings.
4.5.6
To connect the electricity meters
INFORMATION
In case of an electrical meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.